8/34

Motor-starter combinations

Type F starter combinations

2010

CA08103002Z-EN

www.eaton.com

for North America

forNorthAmericaType F startercombinations

Maximum motor rating

Setting range

Rated short-circuit

breaking capacity I

cn

Extension terminal

Motor protective

circuit breaker

Contactor

Alternating current HP

Overload trip Short-circuit

release

240

V 480 Y

277

V

2)

600

Y

347

V

2)

200

V

208

V

230

V

240

V

460

V

480

V

575

V

600

V

Type

Type

Type

HP HP HP HP I

r

I

rm

kA kA

kA

A

A

Modules PKZM0, DIL, BK

1)

0.1 - 0.16

2.2

65

65

50

BK25/3-PKZ0

PKZM0-0,16

DILEM…(…)

0.1 - 0.16

2.2

65

65

50

BK25/3-PKZ0

PKZM0-0,16

DILM7-…(…)

0.16 - 0.25

3.4

65

65

50

BK25/3-PKZ0

PKZM0-0,25

DILEM…(…)

0.16 - 0.25

3.4

65

65

50

BK25/3-PKZ0

PKZM0-0,25

DILM7-…(…)

0.25 - 0.4

5.6

65

65

50

BK25/3-PKZ0

PKZM0-0,4

DILEM…(…)

0.25 - 0.4

5.6

65

65

50

BK25/3-PKZ0

PKZM0-0,4

DILM7-…(…)

0.4 - 0.63

8.8

65

65

50

BK25/3-PKZ0

PKZM0-0,63

DILEM…(…)

0.4 - 0.63

8.8

65

65

50

BK25/3-PKZ0

PKZM0-0,63

DILM7-…(…)

½ ½ 0.63 - 1

14

65

65

50

BK25/3-PKZ0

PKZM0-1

DILEM…(…)

½ ½ 0.63 - 1

14

65

65

50

BK25/3-PKZ0

PKZM0-1

DILM7-…(…)

¾ 1

1 - 1.6

22

65

65

50

BK25/3-PKZ0

PKZM0-1,6

DILEM…(…)

¾ 1

1 - 1.6

22

65

65

50

BK25/3-PKZ0

PKZM0-1,6

DILM7-…(…)

½ ½ 1

1½ 1.6 - 2.5

35

65

65

50

BK25/3-PKZ0

PKZM0-2,5

DILEM…(…)

½ ½ 1

1½ 1.6 - 2.5

35

65

65

50

BK25/3-PKZ0

PKZM0-2,5

DILM7-…(…)

1

1

2

3

2.5 - 4

56

65

65

50

BK25/3-PKZ0

PKZM0-4

DILEM…(…)

1

1

2

3

2.5 - 4

56

65

65

50

BK25/3-PKZ0

PKZM0-4

DILM7-…(…)

1½ 1½ 3

5

4 - 6.3

88

65

65

50

BK25/3-PKZ0

PKZM0-6,3

DILEM…(…)

1½ 1½ 3

5

4 - 6.3

88

65

65

50

BK25/3-PKZ0

PKZM0-6,3

DILM7-…(…)

3

3

7½ 10

6.3 - 11

140

65

65

50

BK25/3-PKZ0

PKZM0-10

DILM9-…(…)

3

3

7½ –

9 - 12

168

65

65

50

BK25/3-PKZ0

PKZM0-12

DILM12-…(…)

3

5

10

10 - 16

224

50

50

BK50/3-PKZ4-E

PKZM0-16

DILM17-…(…)

3

5

10

10 - 16

224

18

18

BK50/3-PKZ4-E

PKZM0-16

DILM17-…(…)

5

5

10

16 - 20

280

18

18

BK50/3-PKZ4-E

PKZM0-20

DILM25-…(…)

5

7½ 15

20 - 25

350

18

18

BK50/3-PKZ4-E

PKZM0-25

DILM25-…(…)

7½ 10

20

25 - 32

448

18

18

BK50/3-PKZ4-E

PKZM0-32

DILM32-…(…)

Modules PKZM4, DIL, BK

3

5

10

15

10 - 16

224

65

65

50

BK50/3-PKZ4-E

PKZM4-16

DILM17-…(…)

5

7½ 15

20

16 - 27

350

65

65

50

BK50/3-PKZ4-E

PKZM4-25

DILM25-…(…)

7½ 10

25

30

24 - 34

448

65

65

50

BK50/3-PKZ4-E

PKZM4-32

DILM32-…(…)

10

15

30

30

32 - 40

560

65

65

50

BK50/3-PKZ4-E

PKZM4-40

DILM40(…)

10

15

30

40 - 52

700

65

65

BK50/3-PKZ4-E

PKZM4-50

DILM50(…)

15

15

40

50 - 56

812

65

65

BK50/3-PKZ4-E

PKZM4-58

DILM65(…)

15

15

40

52 - 58

882

65

65

BK50/3-PKZ4-E

PKZM4-63

DILM65(…)

Notes

Device for world markets IEC ≙ UL/CSA

Service factor (SF)

Set value I

r

on the current scale, depending on the load factor

SF=1.15 -> I

r

= 1 x I

n mot

SF=1.0 -> I

r

= 0.9 x I

n mot

1)

Calculate motor power in this range according to the rated operational current. Stated values to NEC

Table 430 - 150.

2)

Suitable for networks with grounded star-point

Type F starter combinations do not need an upstream protective device.

For use in Canada, the switch must be fitted with an AK-PKZ0.

I

PKZMO, DILM, BK...

HPL08034EN