Table of Contents Table of Contents
Previous Page  289 / 338 Next Page
Information
Show Menu
Previous Page 289 / 338 Next Page
Page Background

D-55

Additional information

Electrical characteristics

Compact NS1600b/3200 fixed

Front or rear connection

Incoming via top or bottom

Busbar drawings supplied by

Schneider Electric

Dd383542.eps

Using the data below, it is possible to determine the size of the copper bars and the

maximum permissible currents when making a front or rear customer connections to

busbars for a vertical, fixed Compact NS1600b/NS3200, taking into account the

ambient temperature around the switchboard and the IP value.

Connection to be made according to the busbar drawings supplied.

For connection cable cross-sections and quantities, see page D-45.

Customer connection

Flat bars, 10 mm thick

Device

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40°C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP>31

NS1600b Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10

bb

I (A)

1560

1480

1520

1430

1480

1380

1430

1330

1380

1280

1330

NS2000 Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10

bb

I (A)

2000

2000

2000

1950

2000

1900

1950

1830

1900

1760

1830

NS2500 Size per phase 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10

bb

I (A)

2470

2280

2410

2210

2350

2140

2280

2070

2210

2000

2140

NS3200 Size per phase 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10

bb

I (A)

2860

2630

2790

2530

2720

2430

2630

2350

2530

2270

2430

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Note:

the values indicated above have been validated for Prisma P switchboards.

Designingcustomerconnections

Fixed Compact NS1600b to NS3200