Table of Contents Table of Contents
Previous Page  285 / 338 Next Page
Information
Show Menu
Previous Page 285 / 338 Next Page
Page Background

D-51

Additional information

Electrical characteristics

Masterpact NW08 to NW16

Drawout

Vertical mounting

Front or rear connection

Incoming via top or bottom

Busbar drawings supplied by

Schneider Electric

Dd383676.eps

Using the data below, it is possible to determine the size of the copper bars and the

maximum permissible currents when making a front or rear customer connections to

busbars for a vertical, drawout Masterpact NT08/NT16, taking into account the

ambient temperature around the switchboard and the IP value.

Connection to be made according to the busbar drawings supplied.

For connection cable cross-sections and quantities, see page D-45.

Customer connection

Flat bars, 5 mm thick

Device

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NW08

Size per phase

2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5

bb

I (A)

800

800

800

800

800

800

800

800

800

800

800

NW10

Size per phase

2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5

bb

I (A)

1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

NW12

Size per phase

2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5

bb

I (A)

1250 1250 1250 1250 1250 1230 1250 1200 1230 1160 1200

NW16

Size per phase

2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5

bb

I (A)

1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Note:

the values indicated above have been validated for Prisma P switchboards.

Designingcustomerconnections

Drawout Masterpact NW08 to NW16