Table of Contents Table of Contents
Previous Page  291 / 338 Next Page
Information
Show Menu
Previous Page 291 / 338 Next Page
Page Background

D-57

Additional information

Electrical characteristics

Compact NS630b to NS1600

Withdrawable

Rear connection

Incoming via top or bottom

Busbar drawings supplied by

Schneider Electric

DD383807.eps

Using the data below, it is possible to determine the size of the copper bars and the

maximum permissible currents when making a rear customer connection for a

vertical, withdrawable Compact NS630b/NS1600, taking into account the ambient

temperature around the switchboard and the IP value.

Connection to be made according to the busbar drawings supplied.

For connection cable cross-sections and quantities, see page D-45.

Customer connection

Flat bars, 5 mm thick

Device

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40°C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NS630b Size per phase 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5

bb

I (A)

630

630

630

630

630

630

630

630

630

630

630

NS800 Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5

bb

I (A)

800

800

800

800

800

800

800

800

800

800

800

NS1000 Size per phase 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5

bb

I (A)

1000 1000 1000 1000 1000 1000 1000 1000 1000 960

1000

NS1250 Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5

bb

I (A)

1250 1250 1250 1250 1250 1230 1250 1180

1230 1130

1180

NS1600 Size per phase 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5

bb

I (A)

1560 1430 1520 1430 1480 1380 1430 1330 1380 1280 1330

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Customer connection

Flat bars, 10 mm thick

Device

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40°C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NS630b Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

bb

I (A)

630

630

630

630

630

630

630

630

630

630

630

NS800 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

bb

I (A)

800

800

800

800

800

800

800

800

800

800

800

NS1000 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

bb

I (A)

1000

1000

1000

1000

1000

1000

1000

1000

1000

960

1000

NS1250 Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10

bb

I (A)

1250

1250

1250

1250

1250

1210

1250

1160

1210

1110

1160

NS1600 Size per phase 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10

bb

I (A)

1560

1430

1520

1430

1480

1380

1430

1330

1380

1280

1330

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Canalis connection

For Canalis connections, apply the appropriate derating coefficient K.

Device

NS630b NS800

NS1000 NS1250 NS1600

Derating coefficient K

1

1

1

1

0,98

Note:

the values indicated above have been validated for Prisma P switchboards.

Designingcustomerconnections

Withdrawable

Compact NS630b to NS1600