![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0289.png)
D-53
Additional information
Electrical characteristics
Masterpact NT06 to NT16
Fixed
Rear connection
Incoming via top or bottom
Busbar drawings supplied by
Schneider Electric
Dd383678.eps
Using the data below, it is possible to determine the size of the copper bars and the
maximum permissible currents when making a front or rear customer connections to
busbars for a vertical, fixed Masterpact NT06/NT16, taking into account the ambient
temperature around the switchboard and the IP value.
Connection to be made according to the busbar drawings supplied.
For connection cable cross-sections and quantities, see page D-45.
Customer connection
Flat bars, 5 mm thick
Device
Permissible current (A)
Ambient temperature around the switchboard
25 °C
30 °C
35 °C
40°C
45 °C
50 °C
IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31
NT06
Size per phase 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5
bb
I (A)
630
630
630
630
630
630
630
630
630
630
630
NT08
Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5
bb
I (A)
800
800
800
800
800
800
800
800
800
800
800
NT10
Size per phase 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5
bb
I (A)
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NT12
Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5
bb
I (A)
1250 1250 1250 1250 1250 1250 1250 1250 1250 1200 1250
NT16
Size per phase 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5
bb
I (A)
1600 1570 1600 1520 1570 1470 1520 1420 1470 1370 1420
bb
Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Customer connection
Flat bars, 10 mm thick
Device
Permissible current (A)
Ambient temperature around the switchboard
25 °C
30 °C
35 °C
40°C
45 °C
50 °C
IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31
NT06 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10
bb
I (A)
630
630
630
630
630
630
630
630
630
630
630
NT08 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10
bb
I (A)
800
800
800
800
800
800
800
800
800
800
800
NT10 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10
bb
I (A)
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
NT12 Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10
bb
I (A)
1250
1250
1250
1250
1250
1250
1250
1250
1250
1180
1230
NT16 Size per phase 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10
bb
I (A)
1600
1570
1600
1520
1570
1470
1520
1420
1470
1370
1420
bb
Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Canalis connection
For Canalis connections, apply the appropriate derating coefficient K.
Device
NT06b
NT08
NT10
NT12
NT16
Derating coefficient K
1
1
1
1
0,98
Note:
the values indicated above have been validated for Prisma P switchboards.
Designingcustomerconnections
Fixed Masterpact NT06 to NT16