Table of Contents Table of Contents
Previous Page  282 / 338 Next Page
Information
Show Menu
Previous Page 282 / 338 Next Page
Page Background

D-48

Compact NS630b to NS1000, fixed

Horizontal mounting

Front or rear connection

Installation on the left or right

Dd383541.eps

Using the data below, it is possible to determine the permissible current for a

prefabricated connection between a horizontal, fixed Compact NS630b/NS1000 and

Linergy busbars depending on the ambient temperature around the switchboard and

the IP value.

Connection transfer assemblies

Device and cat. no.

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40°C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NS630b 3P cat. no. 04483 630

630

630

630

630

630

630

630

630

630

630

bb

4P cat. no. 04484

NS800 3P cat. no. 04483 800

800

800

800

800

800

800

800

800

800

800

bb

4P cat. no. 04484

NS1000 3P cat. no. 04483 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

bb

4P cat. no. 04484

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Note:

the values indicated above have been validated for Prisma P switchboards.

Designingcustomerconnections

Connection transfer assembly for fixed

Compact NS630b to NS1000

Additional information

Electrical characteristics