Table of Contents Table of Contents
Previous Page  277 / 338 Next Page
Information
Show Menu
Previous Page 277 / 338 Next Page
Page Background

D-43

Additional information

Electrical characteristics

Compact NSX100 to NSX630

Insulated flexible copper bars (withstand temperature = 125 °C)

Devices

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31

NSX100

TMD-TMG

Size per phase

20 x 2

20 x 2

20 x 2

20 x 2

20 x 2

20 x 2

I nc (A)

100

100

100

97.5

95

92.5

NSX125

TMD-TMG

Size per phase

20 x 2

20 x 2

20 x 2

20 x 2

20 x 2

20 x 2

I nc (A)

125

125

125

122

119

115

NSX160

(1)

TMD-TMG

Size per phase

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

I nc (A)

160

160

160

156

152

148

NSX250

(1)

TMD-TMG

Size per phase

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

I nc (A)

250

244

238

231

225

219

NSX100

STR

Size per phase

20 x 2

20 x 2

20 x 2

20 x 2

20 x 2

20 x 2

I nc (A)

100

100

100

100

100

100

NSX160

STR

Size per phase

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

I nc (A)

160

160

160

160

160

160

NSX250

(2)

STR

Size per phase

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

I nc (A)

250

245

237

230

225

220

NSX400B/F/N/H/S/L

fixed

Size per phase

32 x 5

32 x 5

32 x 5

32 x 5

32 x 5

32 x 5

I nc (A)

400

400

400

390

380

370

NSX400B/F/N/H/S/L

with Vigi

Size per phase

32 x 5

32 x 5

32 x 5

32 x 5

32 x 5

32 x 5

I nc (A)

400

390

380

370

360

350

NSX400B/F/N/H/S/L

withdrawable

Size per phase

32 x 5

32 x 5

32 x 5

32 x 5

32 x 5

32 x 5

I nc (A)

400

390

380

370

360

350

NSX630B/F/N/H/S/L

fixed

Size per phase

32 x 6

32 x 6

32 x 6

32 x 6

32 x 6

32 x 6

I nc (A)

630

615

600

585

570

550

NSX630B/F/N/H/S/L

with Vigi or

withdrawable

Size per phase

32 x 8

32 x 8

32 x 8

32 x 8

32 x 8

32 x 8

I nc (A)

570

550

535

520

505

490

IP > 31

NSX100

TMD-TMG

Size per phase

20 x 2

20 x 2

20 x 2

20 x 2

20 x 2

20 x 2

I nc (A)

100

100

100

97.5

95

92.5

NSX125

TMD-TMG

Size per phase

20 x 2

20 x 2

20 x 2

20 x 2

20 x 2

20 x 2

I nc (A)

125

125

125

122

119

115

NSX160

(1)

TMD-TMG

Size per phase

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

I nc (A)

160

160

160

156

152

148

NSX250

(1)

TMD-TMG

Size per phase

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

I nc (A)

238

231

225

219

213

207

NSX100

STR

Size per phase

20 x 2

20 x 2

20 x 2

20 x 2

20 x 2

20 x 2

I nc (A)

100

100

100

100

100

100

NSX160

STR

Size per phase

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

I nc (A)

160

160

160

160

160

160

NSX250

(2)

STR

Size per phase

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

I nc (A)

237

230

225

220

215

210

NSX400B/F/N/H/S/L

fixed

Size per phase

32 x 5

32 x 5

32 x 5

32 x 5

32 x 5

32 x 5

I nc (A)

400

400

400

390

380

370

NSX400B/F/N/H/S/L

with Vigi

Size per phase

32 x 5

32 x 5

32 x 5

32 x 5

32 x 5

32 x 5

I nc (A)

400

390

380

370

360

350

NSX400B/F/N/H/S/L

withdrawable

Size per phase

32 x 5

32 x 5

32 x 5

32 x 5

32 x 5

32 x 5

I nc (A)

400

390

380

370

360

350

NSX630B/F/N/H/S/L

fixed

Size per phase

32 x 6

32 x 6

32 x 6

32 x 6

32 x 6

32 x 6

I nc (A)

600

585

570

550

535

520

NSX630B/F/N/H/S/L

with Vigi or

withdrawable

Size per phase

32 x 8

32 x 8

32 x 8

32 x 8

32 x 8

32 x 8

I nc (A)

535

520

505

490

475

420

(1)

For a withdrawable NSX160 or NSX250 equipped with a Vigi or an insulation-monitoring

module, multiply the In values by 0.9.

(2)

For a withdrawable NSX250 equipped with a Vigi or an insulation-monitoring module, multiply

the In values by 0.86.

To connect a Compact NSX250 to a Linergy BW busbars, use a 24 x 5 flexible bar

cat. no. 04746.

Note:

the values indicated above have been validated for Prisma P switchboards.

Designing connections

y

630 A

Compact circuit breakers

NSX100 to NSX630

Insulated flexible copper bars