D-45

Additional information

Electrical characteristics

Tubular lugs for incoming

connection blocks

Maximum size of lugs for connection to the different incoming connection blocks.

Standard Cu

lugs

Narrow Cu

lugs

Narrow

bimetal lugs

Incoming connection block for

Compact NSX-INS250 supplied via the top or the

bottom, cat. no. 04066 et 04067

150 mm²

240 mm²

185 mm²

In-duct incoming connection block for

Compact NSX630 supplied via the top or the

bottom cat. no. 04076

240 mm²

300 mm²

300 mm²

DD382788.eps

Narrow bimetal lugs

Cat. no. selection

Cat. no.

Cable size

(mm²)

Quantity

Lugs for aluminium cable

(1)

29504

150

3

29505

150

4

29506

185

3

29507

185

4

32504

240

3

32505

240

4

32506

300

3

32507

300

4

(1)

Supplied with 2 or 3 interphase barriers.

Customer connection

of devices

u

630 A

Maximum size and number of cables for connection to terminal extension bars

(according to busbar drawing supplied) for customer connection of Compact NSX

and Masterpact NT/NW devices.

Cable size

(mm²)

Quantity

Size and number of cables

Copper lugs

300

12

Bimetal lugs

240

12

Designing cable connections

Tubular lugs