Additional information

Electrical characteristics

Compact NSX100 to NSX630

Copper cable, withstand temperature = 105 °C

Devices

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31

NSX100

TMD-TMG

Size per phase

50 mm²

50 mm²

50 mm²

50 mm²

50 mm²

50 mm²

I nc (A)

100

100

100

97.5

95

92.5

NSX125

TMD-TMG

Size per phase

70 mm²

70 mm²

70 mm²

70 mm²

70 mm²

70 mm²

I nc (A)

125

125

125

122

119

115

NSX160

(1)

TMD-TMG

Size per phase

95 mm²

95 mm²

95 mm²

95 mm²

95 mm²

95 mm²

I nc (A)

160

160

160

156

152

148

NSX250

(1)

TMD-TMG

Size per phase

120 mm²

120 mm²

120 mm²

120 mm²

120 mm²

120 mm²

I nc (A)

250

244

238

231

225

219

NSX100

STR

Size per phase

50 mm²

50 mm²

50 mm²

50 mm²

50 mm²

50 mm²

I nc (A)

100

100

100

100

100

100

NSX160

STR

Size per phase

95 mm²

95 mm²

95 mm²

95 mm²

95 mm²

95 mm²

I nc (A)

160

160

160

160

160

160

NSX250

(2)

STR

Size per phase

120 mm²

120 mm²

120 mm²

120 mm²

120 mm²

120 mm²

I nc (A)

250

245

237

230

225

220

IP > 31

NSX100

TMD-TMG

Size per phase

50 mm²

50 mm²

50 mm²

50 mm²

50 mm²

50 mm²

I nc (A)

100

100

100

97.5

95

92.5

NSX125

TMD-TMG

Size per phase

70 mm²

70 mm²

70 mm²

70 mm²

70 mm²

70 mm²

I nc (A)

125

125

125

122

119

115

NSX160

(1)

TMD-TMG

Size per phase

95 mm²

95 mm²

95 mm²

95 mm²

95 mm²

95 mm²

I nc (A)

160

160

160

156

152

148

NSX250

(1)

TMD-TMG

Size per phase

120 mm²

120 mm²

120 mm²

120 mm²

120 mm²

120 mm²

I nc (A)

237

230

225

220

215

210

NSX100

STR

Size per phase

50 mm²

50 mm²

50 mm²

50 mm²

50 mm²

50 mm²

I nc (A)

100

100

100

100

100

100

NSX160

STR

Size per phase

95 mm²

95 mm²

95 mm²

95 mm²

95 mm²

95 mm²

I nc (A)

160

160

160

160

160

160

NSX250

(2)

STR

Size per phase

120 mm²

120 mm²

120 mm²

120 mm²

120 mm²

120 mm²

I nc (A)

237

230

225

220

215

210

(1)

For a withdrawable NSX160 or NSX250 equipped with a Vigi or an insulation-monitoring

module, multiply the In values by 0.9.

(2)

For a withdrawable NSX250 equipped with a Vigi or an insulation-monitoring module, multiply

the In values by 0.86.

Note:

the values indicated above have been validated for Prisma P switchboards.

Note:

Schneider Electric recommends connecting Compact NSX400/630 circuit breakers with

insulated flexible bars or rigid bars (see page D-43).

Designing connections

y

630 A

Compact circuit breakers

NSX100 to NSX630

Copper cable

Cables: pratical guidelines

This section doesn’t concern customer’s loads connection (see IEC 61439-1,

IEC 60364).

Schneider Electric provides cabling recommendations according to the rating of the

circuit breaker.

The size of cables must be selected according to:

b

the level of current

b

the ambient temperature around the conductors

b

the degree of protection for the switchboard.

The tables below take into account the installation conditions for each type of device

(permissible temperature at connection terminals, etc.).

They follow the temperature derating values for installed devices in all cubicles with

cover panels rated IP

y

55.

b

switchboard internal temperature 60 °C

b

connections using copper cables.

The withstand temperature of insulating material of cable = 105°C.