D-40

Additional information

Electrical characteristics

Connection

Flat bars, 10 mm thick

Device

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NS630b Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

bb

I (A)

630

630

630

630

630

630

630

630

630

630

630

NS800 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

bb

I (A)

800

800

800

800

800

800

800

800

800

800

800

NS1000 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

bb

I (A)

1000

1000

1000

1000

1000

1000

1000

1000

1000

960

1000

NS1250 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

bb

I (A)

1250

1250

1250

1250

1250

1210

1250

1160

1210

1110

1160

NS1600

(1)

Size per phase 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10

bb

I (A)

1560

1430

1520

1430

1480

1380

1430

1330

1380

1280

1330

(1)

Make the neutral connection with one bar, 50 x 10 mm.

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Horizontal link

Flat bars, 10 mm thick

Device

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NS630b Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

bb

I (A)

630

630

630

630

630

630

630

630

630

630

630

NS800 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

bb

I (A)

800

800

800

800

800

800

800

800

800

800

800

NS1000 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

bb

I (A)

1000

1000

1000

1000

1000

1000

1000

1000

1000

970

1000

NS1250 Size per phase 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10

bb

I (A)

1250

1250

1250

1250

1250

1210

1250

1160

1210

1110

1160

NS1600 Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10

bb

I (A)

1560

1430

1520

1430

1480

1380

1430

1330

1380

1280

1330

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Note:

the values indicated above have been validated for Prisma P switchboards.

Designing connections between

a device and busbars

Withdrawable

Compact NS630b to NS1600