Additional information

Electrical characteristics

Compact NS630b to NS1000

Horizontal mounting

Vertical Linergy LGYE, LGY, BS busbars

Dd383538.eps

Using the data below, it is possible to determine the size of the copper bars and

the maximum permissible currents when making the connections to busbars for

a horizontal, fixed Compact NS630b/NS1000, taking into account the ambient

temperature around the switchboard and the IP value.

Flat bars, 5 mm thick

Device

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NS630b Size per phase 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5

bb

I (A)

630

630

630

630

630

630

630

630

630

630

630

NS800 Size per phase 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5

bb

I (A)

800

800

800

800

800

800

800

800

800

800

800

NS1000 Size per phase 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5

bb

I (A)

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Flat bars, 10 mm thick

Device

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

NS630b Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

bb

I (A)

630

630

630

630

630

630

630

630

630

630

630

NS800 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

bb

I (A)

800

800

800

800

800

800

800

800

800

800

800

NS1000 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

bb

I (A)

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Note:

the values indicated above have been validated for Prisma P switchboards.

Designing connections between

a device and busbars

Horizontal, fixed

Compact NS630b to NS1000