Table of Contents Table of Contents
Previous Page  281 / 338 Next Page
Information
Show Menu
Previous Page 281 / 338 Next Page
Page Background

D-47

Additional information

Electrical characteristics

Masterpact NT06 to NT16

Vertical mounting

Front or rear connection

Incoming via top or bottom

Dd383673.eps

Using the data below, it is possible to determine the permissible current for a

prefabricated connection between a vertical Masterpact NT06/NT16, fixed or

drawout, and Linergy busbars depending on the ambient temperature around the

switchboard and the IP value.

Fixed

Prefabricated connections

Device and cat. no.

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NT06 3P cat. no. 33642

630

630

630

630

630

630

630

630

630

630

630

bb

4P cat. no. 33643

NT08 3P cat. no. 33642

800

800

800

800

800

800

800

800

800

800

800

bb

4P cat. no. 33643

NT10 3P cat. no. 33642

1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

bb

4P cat. no. 33643

NT12 3P réf.33642 + 33644 1250 1250 1250 1250 1250 1250 1250 1200 1250 1150 1200

bb

4P réf.33643 + 33645

NT16 3P réf.33642 + 33644 1600 1570 1600 1520 1570 1470 1520 1420 1470 1370 1420

bb

4P réf.33643 + 33645

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Withdrawable

Prefabricated connections

Device and cat. no.

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NT06 3P cat. no. 33642

630

630

630

630

630

630

630

630

630

630

630

bb

4P cat. no. 33643

NT08 3P cat. no. 33642

800

800

800

800

800

800

800

800

800

800

800

bb

4P cat. no. 33643

NT10 3P cat. no. 33642

1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

bb

4P cat. no. 33643

NT12 3P réf.33642 + 33644 1250 1250 1250 1250 1250 1250 1250 1200 1250 1150 1200

bb

4P réf.33643 + 33645

NT16 3P réf.33642 + 33644 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330

bb

4P réf.33643 + 33645

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Note:

the values indicated above have been validated for Prisma P switchboards.

Designingcustomerconnections

Prefabricated connections for

Masterpact NT06 to NT16