Additional information

Electrical characteristics

Drawout Masterpact NT06 to NT16

Rear connection

Incoming via top or bottom

Busbar drawings supplied by

Schneider Electric

Dd383679.eps

Using the data below, it is possible to determine the size of the copper bars and the

maximum permissible currents when making a customer connections to busbars for

a vertical, drawout Masterpact NT06/NT16, taking into account the ambient

temperature around the switchboard and the IP value.

Connection to be made according to the busbar drawings supplied.

For connection cable cross-sections and quantities, see page D-45.

Customer connection

Flat bars, 5 mm thick

Device

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40°C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NT06

Size per phase 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5

bb

I (A)

630

630

630

630

630

630

630

630

630

630

630

NT08

Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5

bb

I (A)

800

800

800

800

800

800

800

800

800

800

800

NT10

Size per phase 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5

bb

I (A)

1000 1000 1000 1000 1000 1000 1000 1000 1000 960

1000

NT12

Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5

bb

I (A)

1250 1250 1250 1250 1250 1230 1250 1180

1230 1130

1180

NT16

Size per phase 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5

bb

I (A)

1560 1430 1520 1430 1480 1380 1430 1330 1380 1280 1330

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Customer connection

Flat bars, 10 mm thick

Device

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40°C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NT06 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

bb

I (A)

630

630

630

630

630

630

630

630

630

630

630

NT08 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

bb

I (A)

800

800

800

800

800

800

800

800

800

800

800

NT10 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

bb

I (A)

1000

1000

1000

1000

1000

1000

1000

1000

1000

960

1000

NT12 Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10

bb

I (A)

1250

1250

1250

1250

1250

1210

1250

1160

1210

1110

1160

NT16 Size per phase 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10

bb

I (A)

1560

1430

1520

1430

1480

1380

1430

1330

1380

1280

1330

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Canalis connection

For Canalis connections, apply the appropriate derating coefficient K.

Device

NT06

NT08

NT10

NT12

NT16

Derating coefficient K

1

1

1

1

0,98

Note:

the values indicated above have been validated for Prisma P switchboards.

Designingcustomerconnections

Drawout Masterpact NT06 to NT16