D-62
Additional information
Electrical characteristics
Designing busbars
Fupact INF, ISFT
Vertical Linergy BS busbars
Lateral Linergy BS busbars
Fupact INF/ISFT
Linergy BS bars, 5 mm thick
Type of bars
Permissible current (A)
Ambient temperature around the switchboard
25 °C
30 °C
35 °C
40 °C
45 °C
50 °C
Size per phase
IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31
1 Linergy BS bar, 60 x 5
800
750
760
700
710
650
660
600
610
550
560
bb
1 Linergy BS bar, 80 x 5
1000 910
970
860
910
810
860
750
810
700
750
bb
2 Linergy BS bars, 60 x 5
1400 1250 1320 1160 1250 1070 1160 980
1070 880
980
bb
2 Linergy BS bars, 80 x 5
1700 1500 1600 1400 1500 1280 1400 1160 1280 1030 1160
bb
bb
Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Linergy BS bars, 10 mm thick
Type of bars
Permissible current (A)
Ambient temperature around the switchboard
25 °C
30 °C
35 °C
40 °C
45 °C
50 °C
Size per phase
IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31
1 Linergy BS bar, 50 x 10
1150 1000 1080 930
1000 850
930
760
850
670
760
bb
1 Linergy BS bar, 60 x 10
1400 1250 1320 1160 1250 1070 1160 980
1070 880
980
bb
1 Linergy BS bar, 80 x 10
1700 1500 1600 1400 1500 1280 1400 1160 1280 1030 1160
bb
2 Linergy BS bars, 50 x 10
1940 1690 1810 1560 1700 1420 1560 1270 1420 1100 1270
bb
2 Linergy BS bars, 60 x 10
2170 1900 2040 1750 1900 1590 1750 1420 1590 1240 1420
bb
2 Linergy BS bars, 80 x 10
2670 2340 2500 2160 2340 1970 2160 1770 1970 1550 1770
bb
2 x 1 Linergy BS bar, 80 x 10 3020 2650 2840 2450 2650 2230 2450 2010 2230 1760 2010
bb
bb
Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.