![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0150.png)
B-14
Linergy LGY
Lateral profiles up to 3200A
400 mm deep installation
Linergy LGY profiles
Up to 1600 A (simple busbars)
Up to 3200 A (double busbars)
In duct
W150
2 x W150
Linergy profiles, 1670 mm wide
Dd381233-LIN-7.eps
DD381234-LIN-7.eps
DD381235-LIN-7.eps
DD385495.eps
DD385496.eps
DD381235-LIN-7.eps
DD385495.eps
DD385496.eps
630 A 800 A 1000 A 1250 A 1600 A 2 x 1000 A
2 x 1250 A 2 x 1600 A
Permissible current for an ambient
temperature of 35 °C around the
switchboard
IP
y
31 680 A 840 A 1040 A 1290 A 1650 A 2000 A
2500 A
3200 A
IP > 31 590 A 760 A 950 A 1170 A 1480 A 1820 A
2260 A
2920 A
Number of profiles per phase
1
2
Catalogue numbers
04502 04503 04504 04505 04506 04504
04505
04506
Busbar supports
700mm
maxi
700mm
maxi
387,5mm
maxi
DD381509New_modif-LIN-25.eps
DD380741-LIN.eps
Fixed support
04651
Characteristics
DD380742-LIN-12.eps
An end stop must be installed on the bottom support:
01109
(set of 12).
Number of
supports
depending
on Icw (kA
rms/1 s)
y
25 3
2 x 3
y
30 -
3
2 x 3
y
40 -
3
2 x 3
y
50 -
4
2 x 3
y
60 -
5
2 x 4
y
65 -
5
2 x 4
y
75 -
7
2 x 5
y
85 -
8
2 x 5
Catalogue
numbers
Fixed support
04651
Chock
01109
Equipotential links
DD382327R-20.eps
3 equipments must
be installed
between the
busbars.
-
DD382576-LIN-30.eps
Connection
made with a flat
80 x 10 mm
busbar between
2 W150 ducts
Connections to the horizontal Linergy BS busbars
DD385427.eps
Characteristics
Mounting hardware supplied. Order 1 link per phase
Cat. no.
according to
horizontal
busbar size
Thickness 5 mm
04634
(1000 A)
04635
(1600 A)
-
Thickness
10 mm
W
y
80 mm
04636
2 x
04636
W 100 mm
04636
+
04642
(2)
2 x
04636
+ 2 x
04642
W 120 mm
04638
2 x
04638
Connections to the horizontal Linergy LGYE busbars
DD384557.EPS
y
1600 A
Characteristics
Supplied with mounting hardware.
Catalogue numbers include 1 connection only: 1 connection per phase.
Cat. no. according to horizontal busbar size 04602
(vertical connection)
04603
(vertical shifted connection)
(1)
(1)
Dedicated connection 04603 for Linergy LGYE busbar in 150 mm duct with horizontal jointing
(2)
04642
: mounting hardware for bars > 80 mm. Comprises 2 threaded rods.
Distribution
Power busbars