B-14

Linergy LGY

Lateral profiles up to 3200A

400 mm deep installation

Linergy LGY profiles

Up to 1600 A (simple busbars)

Up to 3200 A (double busbars)

In duct

W150

2 x W150

Linergy profiles, 1670 mm wide

Dd381233-LIN-7.eps

DD381234-LIN-7.eps

DD381235-LIN-7.eps

DD385495.eps

DD385496.eps

DD381235-LIN-7.eps

DD385495.eps

DD385496.eps

630 A 800 A 1000 A 1250 A 1600 A 2 x 1000 A

2 x 1250 A 2 x 1600 A

Permissible current for an ambient

temperature of 35 °C around the

switchboard

IP

y

31 680 A 840 A 1040 A 1290 A 1650 A 2000 A

2500 A

3200 A

IP > 31 590 A 760 A 950 A 1170 A 1480 A 1820 A

2260 A

2920 A

Number of profiles per phase

1

2

Catalogue numbers

04502 04503 04504 04505 04506 04504

04505

04506

Busbar supports

700mm

maxi

700mm

maxi

387,5mm

maxi

DD381509New_modif-LIN-25.eps

DD380741-LIN.eps

Fixed support

04651

Characteristics

DD380742-LIN-12.eps

An end stop must be installed on the bottom support:

01109

(set of 12).

Number of

supports

depending

on Icw (kA

rms/1 s)

y

25 3

2 x 3

y

30 -

3

2 x 3

y

40 -

3

2 x 3

y

50 -

4

2 x 3

y

60 -

5

2 x 4

y

65 -

5

2 x 4

y

75 -

7

2 x 5

y

85 -

8

2 x 5

Catalogue

numbers

Fixed support

04651

Chock

01109

Equipotential links

DD382327R-20.eps

3 equipments must

be installed

between the

busbars.

-

DD382576-LIN-30.eps

Connection

made with a flat

80 x 10 mm

busbar between

2 W150 ducts

Connections to the horizontal Linergy BS busbars

DD385427.eps

Characteristics

Mounting hardware supplied. Order 1 link per phase

Cat. no.

according to

horizontal

busbar size

Thickness 5 mm

04634

(1000 A)

04635

(1600 A)

-

Thickness

10 mm

W

y

80 mm

04636

2 x

04636

W 100 mm

04636

+

04642

(2)

2 x

04636

+ 2 x

04642

W 120 mm

04638

2 x

04638

Connections to the horizontal Linergy LGYE busbars

DD384557.EPS

y

1600 A

Characteristics

Supplied with mounting hardware.

Catalogue numbers include 1 connection only: 1 connection per phase.

Cat. no. according to horizontal busbar size 04602

(vertical connection)

04603

(vertical shifted connection)

(1)

(1)

Dedicated connection 04603 for Linergy LGYE busbar in 150 mm duct with horizontal jointing

(2)

04642

: mounting hardware for bars > 80 mm. Comprises 2 threaded rods.

Distribution