![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0148.png)
B-12
Linergy LGYE
Horizontal profiles up to 4000 A
400 mm deep installation
Distribution
Power busbars
Linergy LGYE profiles
Installation
Up to 1600 A
Up to 2500 A
Up to 4000 A
Linergy profiles, 2000 mm wide
60
23
DD385353.eps
60
23
DD385352.eps
60
23
DD385351.eps
60
23
DD385349.eps
60
23
DD385350.eps
100
31
DD385354.eps
100
31
DD385355.eps
150
31
DD385356.eps
150
31
DD385357.eps
630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A
Permissible current for an ambient
temperature of 35 °C around the
switchboard
IP
y
31 630 A 800 A 1000 A 1250 A 1650 A 2000 A
2440 A
3200 A 3620
IP > 31 530 A 680 A 850 A 1050 A 1480 A 1650 A
2100 A
2800 A 3350
Number of profiles per phase
1
Total number of vertical modules (50 mm)
3
3
4
Catalogue numbers
04560 04561 04562 04563 04564 04565
04566
04567
04568
Busbar supports
DD384520-LIN.eps
04662
04664
DD381226-LIN.eps
DD381225-LIN.eps
DD385513.eps
DD385514.eps
Fixed support
04664
Free support
04662
Fixed support
04665
Free support
04678
Characteristics
Two fixed supports for 650 mm or 650 + 150 mm wide Prisma P frameworks and one fixed support for 300/400
mm wide Prisma P frameworks are mandatory. If more supports are required, use free supports.
Note:
in case of 600 mm depth with 115 mm between centers, replace
04664
fixed support by
04665
and
04662
free support by
04678.
In cubicle
W = 650 or
W = 650+150
busbar
supports
75 mm between
centres
Number of
supports
depending on
Icw
(
kA rms/1 s)
y
15
2
y
25 2
y
30 2
y
40 -
2
y
50 -
2
y
60 -
2+1
2
y
65 -
2+1
y
75 -
2+1
y
85 -
2+1
y
100 -
2+2
Catalogue
numbers
Fixed support
04664
04664
+
04671
(1)
(hardware)
04664
+
04646
(2)
(hardware)
Free support
04662
04662
+
04671
(1)
(hardware)
04662
+
04646
(2)
(hardware)
In duct
W = 300
busbar
supports
75 mm between
centres
Number of supports
depending on Icw
(kA rms/1 s)
y
60 1
y
85 1 + 1
y
100 -
1 + 1
Catalogue
numbers
Fixed support
04664
04664
+
04671
(1)
(hardware)
04664
+
04646
(2)
(hardware)
Free support
04662
04662
+
04671
(1)
(hardware)
04662
+
04646
(2)
(hardware)
In duct
W = 400
busbar
supports
75 mm between
centres
Number of supports
depending on Icw
(kA rms/1 s)
y
50 1
y
85 1 + 1
y
100 -
1 + 1
Catalogue
numbers
Fixed support
04664
04664
+
04671
(1)
(hardware)
04664
+
04646
(2)
(hardware)
Free support
04662
04662
+
04671
(1)
(hardware)
04662
+
04646
(2)
(hardware)
(1)
04671
: mounting hardware for bars or profile H = 100 or 120 mm. Comprises 2 threaded rods and 4 insulators.
(2)
04646
: mounting hardware for bars or profile H = 150 mm. Comprises 12 threaded rods and 24 insulators
Joints
Up to 1600 A
Up to 2500 A
Up to 4000 A
630 A
800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A
4000 A
DD384535-LIN.eps
04620
DD384588-LIN.eps
04623
DD384615-LIN.eps
04624
Catalogue numbers
3x
04620
(3P)
4x
04620
+
04624
(4P)
3x
04621
(3P)
4x
04621
+
04624
(4P)
3x
04623
(3P)
4x
04623
+
04624
(4P)
Note
04624
is mandatory in case of jointed 4P Linergy LGYE busbars installations and must be installed only at the junction on
side-by-side frameworks combination. When installed at the bottom of cubicles, the busbars must be partitioned.
Note:
for accesories, see page B-19.