Table of Contents Table of Contents
Previous Page  146 / 338 Next Page
Information
Show Menu
Previous Page 146 / 338 Next Page
Page Background

B-12

Linergy LGYE

Horizontal profiles up to 4000 A

400 mm deep installation

Distribution

Power busbars

Linergy LGYE profiles

Installation

Up to 1600 A

Up to 2500 A

Up to 4000 A

Linergy profiles, 2000 mm wide

60

23

DD385353.eps

60

23

DD385352.eps

60

23

DD385351.eps

60

23

DD385349.eps

60

23

DD385350.eps

100

31

DD385354.eps

100

31

DD385355.eps

150

31

DD385356.eps

150

31

DD385357.eps

630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A

Permissible current for an ambient

temperature of 35 °C around the

switchboard

IP

y

31 630 A 800 A 1000 A 1250 A 1650 A 2000 A

2440 A

3200 A 3620

IP > 31 530 A 680 A 850 A 1050 A 1480 A 1650 A

2100 A

2800 A 3350

Number of profiles per phase

1

Total number of vertical modules (50 mm)

3

3

4

Catalogue numbers

04560 04561 04562 04563 04564 04565

04566

04567

04568

Busbar supports

DD384520-LIN.eps

04662

04664

DD381226-LIN.eps

DD381225-LIN.eps

DD385513.eps

DD385514.eps

Fixed support

04664

Free support

04662

Fixed support

04665

Free support

04678

Characteristics

Two fixed supports for 650 mm or 650 + 150 mm wide Prisma P frameworks and one fixed support for 300/400

mm wide Prisma P frameworks are mandatory. If more supports are required, use free supports.

Note:

in case of 600 mm depth with 115 mm between centers, replace

04664

fixed support by

04665

and

04662

free support by

04678.

In cubicle

W = 650 or

W = 650+150

busbar

supports

75 mm between

centres

Number of

supports

depending on

Icw

(

kA rms/1 s)

y

15

2

y

25 2

y

30 2

y

40 -

2

y

50 -

2

y

60 -

2+1

2

y

65 -

2+1

y

75 -

2+1

y

85 -

2+1

y

100 -

2+2

Catalogue

numbers

Fixed support

04664

04664

+

04671

(1)

(hardware)

04664

+

04646

(2)

(hardware)

Free support

04662

04662

+

04671

(1)

(hardware)

04662

+

04646

(2)

(hardware)

In duct

W = 300

busbar

supports

75 mm between

centres

Number of supports

depending on Icw

(kA rms/1 s)

y

60 1

y

85 1 + 1

y

100 -

1 + 1

Catalogue

numbers

Fixed support

04664

04664

+

04671

(1)

(hardware)

04664

+

04646

(2)

(hardware)

Free support

04662

04662

+

04671

(1)

(hardware)

04662

+

04646

(2)

(hardware)

In duct

W = 400

busbar

supports

75 mm between

centres

Number of supports

depending on Icw

(kA rms/1 s)

y

50 1

y

85 1 + 1

y

100 -

1 + 1

Catalogue

numbers

Fixed support

04664

04664

+

04671

(1)

(hardware)

04664

+

04646

(2)

(hardware)

Free support

04662

04662

+

04671

(1)

(hardware)

04662

+

04646

(2)

(hardware)

(1)

04671

: mounting hardware for bars or profile H = 100 or 120 mm. Comprises 2 threaded rods and 4 insulators.

(2)

04646

: mounting hardware for bars or profile H = 150 mm. Comprises 12 threaded rods and 24 insulators

Joints

Up to 1600 A

Up to 2500 A

Up to 4000 A

630 A

800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A

4000 A

DD384535-LIN.eps

04620

DD384588-LIN.eps

04623

DD384615-LIN.eps

04624

Catalogue numbers

3x

04620

(3P)

4x

04620

+

04624

(4P)

3x

04621

(3P)

4x

04621

+

04624

(4P)

3x

04623

(3P)

4x

04623

+

04624

(4P)

Note

04624

is mandatory in case of jointed 4P Linergy LGYE busbars installations and must be installed only at the junction on

side-by-side frameworks combination. When installed at the bottom of cubicles, the busbars must be partitioned.

Note:

for accesories, see page B-19.