![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0153.png)
B-17
Linergy LGY
Rear profiles up to 1600 A
Distribution
Power busbars
Linergy LGY profiles
Up to 1600 A
At the rear of the cubicle
W650
Linergy profile, 1670 mm wide
Dd381233-LIN-7.eps
DD381234-LIN-7.eps
DD381235-LIN-7.eps
DD385495.eps
DD385496.eps
630 A
800 A
1000 A
1250 A
1600 A
Permissible current for an ambient
temperature of 35 °C around the switchboard
IP
y
31 680 A
840 A
1040 A
1290 A
1650 A
IP > 31 590 A
760 A
950 A
1170 A
1480 A
Number of profiles per phase
1
Catalogue numbers
04502
04503
04504
04505
04506
Busbar supports
350mm
maxi
350mm
maxi
350mm
maxi
350mm
maxi
387,5mm
maxi
DD381241New_modif-LIN.eps
DD381242-LIN.eps
Fixed support
04652
Number of
supports
depending
on Icw
(kA rms/1 s)
y
25 3
y
30 -
4
y
40 -
5
y
50 -
7
Characteristics
DD381243-LIN.eps
Stop to be installed on the bottom support.
01109
(set of 12).
Catalogue numbers
Fixed support
04652
Chock
01109
Connections to the horizontal Linergy BS flat busbars
DD381244-LIN.eps
9C-DD381245-ret-LIN.eps
Connection
04635
to horizontal busbars
5 mm thick.
Connection
04636
to horizontal busbars
10 mm thick.
Characteristics
Mounting hardware supplied, order 1 connection per phase.
For part of the connection, flexible insulated busbars are needed.
Cat. no. according
to horizontal
busbar size
Thickness 5 mm
04635
Thickness
10 mm
W
y
80 mm
04636
W > 80 mm
04636
+
04642
Connections to the horizontal Linergy LGYE flat busbars
DD384611.EPS
Connection
04602
to horizontal Linergy LGYE busbars
5 mm thick.
Characteristics
Mounting hardware supplied, order 1 connection per phase.
For part of the connection, flexible insulated busbars are needed.
Catalogue
numbers
04602