Table of Contents Table of Contents
Previous Page  151 / 338 Next Page
Information
Show Menu
Previous Page 151 / 338 Next Page
Page Background

B-17

Linergy LGY

Rear profiles up to 1600 A

Distribution

Power busbars

Linergy LGY profiles

Up to 1600 A

At the rear of the cubicle

W650

Linergy profile, 1670 mm wide

Dd381233-LIN-7.eps

DD381234-LIN-7.eps

DD381235-LIN-7.eps

DD385495.eps

DD385496.eps

630 A

800 A

1000 A

1250 A

1600 A

Permissible current for an ambient

temperature of 35 °C around the switchboard

IP

y

31 680 A

840 A

1040 A

1290 A

1650 A

IP > 31 590 A

760 A

950 A

1170 A

1480 A

Number of profiles per phase

1

Catalogue numbers

04502

04503

04504

04505

04506

Busbar supports

350mm

maxi

350mm

maxi

350mm

maxi

350mm

maxi

387,5mm

maxi

DD381241New_modif-LIN.eps

DD381242-LIN.eps

Fixed support

04652

Number of

supports

depending

on Icw

(kA rms/1 s)

y

25 3

y

30 -

4

y

40 -

5

y

50 -

7

Characteristics

DD381243-LIN.eps

Stop to be installed on the bottom support.

01109

(set of 12).

Catalogue numbers

Fixed support

04652

Chock

01109

Connections to the horizontal Linergy BS flat busbars

DD381244-LIN.eps

9C-DD381245-ret-LIN.eps

Connection

04635

to horizontal busbars

5 mm thick.

Connection

04636

to horizontal busbars

10 mm thick.

Characteristics

Mounting hardware supplied, order 1 connection per phase.

For part of the connection, flexible insulated busbars are needed.

Cat. no. according

to horizontal

busbar size

Thickness 5 mm

04635

Thickness

10 mm

W

y

80 mm

04636

W > 80 mm

04636

+

04642

Connections to the horizontal Linergy LGYE flat busbars

DD384611.EPS

Connection

04602

to horizontal Linergy LGYE busbars

5 mm thick.

Characteristics

Mounting hardware supplied, order 1 connection per phase.

For part of the connection, flexible insulated busbars are needed.

Catalogue

numbers

04602