Table of Contents Table of Contents
Previous Page  152 / 338 Next Page
Information
Show Menu
Previous Page 152 / 338 Next Page
Page Background

B-18

Linergy BS

rear busbars up to 1600 A

Distribution

Power busbars

Flat bars

Up to 1600 A

At the rear of the cubicle

L650

Copper with holes,

1670 mm wide

DD381505-LIN.eps

800 A

1000 A 1400 A 1800 A 1000 A 1200 A 1600 A

Permissible current for an ambient temperature

of 35 °C around the switchboard

IP

y

31

800 A

1000 A 1400 A 1800 A -

-

-

IP > 31

750 A

900 A

1250 A 1600 A 1080 A 1250 A

1600 A

Size of bars (mm)

60 x 5

80 x 5

60 x 5

80 x 5

50 x 10

60 x 10

80 x 10

Number of bars per phase

1

2

1

Catalogue numbers

04516

04518

04516

04518

04525

04526

04528

Busbar supports

DD380732-LIN.eps

DD381652-LIN.eps

DD380734.eps

Fixed busbar supports

04653

Free busbar supports

04662

Mounting chocks

04669

PP

PD[L

PP

PD[L

PP

PD[L

PP

PD[L

PP

PD[L

PP

PD[L

DD381503New_modif-LIN.eps

Characteristics

Three fixed supports cat. no. 04653 are required to maintain the busbars.

If more than three supports are required, use additional free supports cat. no. 04662.

Ametal mounting chock, cat. no. 04669 (set of 100) 5 mm thick, is screwed to the bar. It rests on a

fixed support and maintains the position of the bar.

DD380815-LIN.eps

Chock: 1 bar/phase

DD380733-LIN.eps

Chock: 2 bars/phase

Number of

supports

depending

on Icw

(kA rms/1 s)

y

15

3

3

y

25

3+2

3

3

y

30

3+2

3+2

y

40

3+4

3+2

3+2

y

50

-

3+4

3+2

y

60

-

3+4

y

65

-

3+4

y

75

-

-

3+6

y

85

-

-

Catalogue numbers

04653

(fixed) +

04662

(free) +

04669

(chock)

Connections to the horizontal Linergy BS flat busbars

DD380730.eps

Connection

04636

to horizontal busbars

Thickness 5 mm

Connection

04636

to horizontal busbars

Thickness 10 mm

Characteristics

For part of the connection, flexible insulated busbars are needed.

Catalogue numbers

04635

and

04636

include 1 connection only = 1 connection per phase.

Reference 04642 consists of 2 M8 x 140 screws which can replace the original M8 x 120 screws.

Cat. no.

according to

horizontal

busbar size

Thickness 5 mm

04635

Thickness

10 mm

W

y

80 mm

04636

(1)

W > 80 mm

04636

+

04642

(1)

(1)

To be made.