B-19
Linergy
Accessories
Distribution
Power busbars
Accessories
DD385390.eps
DD381219-LIN-15.eps
DD381222-LIN-10.eps
DD385391.eps
DD385392.eps
Linergy conn. hardware Flat washers
Markers
Sheets
Linergy
connection
hardware
Characteristics
Set of 20: 20 bolts + 20 nuts + 20 contact washers, class 8.8.
The screws slide into the profile and are then locked in the desired position.
Catalogue
numbers
Width 25 mm
04766
Width 39 mm
04767
Steel flat
washers
Characteristics
M8 set of 20
Catalogue
numbers
20 mm ext. Ø
04772
24 mm ext. Ø
04773
28 mm ext. Ø
04774
Brass flat
washers
Characteristics
M8 sold in lots of 20 for connection of
y
25 mm
2
lugs to Linergy
Cat. no.
20 mm ext. Ø
04775
Markers
Characteristics
12 clip-on supports + N, L1, L2, L3, PE, PEN labels
Catalogue numbers
04794
Characteristics
Linergy LGYE busbars connection kit spare part
Catalogue numbers
01130
Sheets
Characteristics
Set of 12 flat plates with 2 studs + 24 torque nuts + 24 contact washers
The plates slide along the profile.
Cat. no.
2 studs
04768
Characteristics
Set of 8 flat plates with 3 studs + 24 torque nuts + 24 contact washers
The plates slide along the profile.
Cat. no.
3 studs
04769
M8 bolts
DD380737.eps
Linergy BS,
20 bolts
class 8.8
Characteristics
Set of 20 bolts + 20 nuts + 40 contact washers.
Catalogue
numbers
M8 x 20
04782
M8 x 25
04783
M8 x 30
04784
M8 x 35
04785
M8 x 40
04786
M8 x 45
04787
M8 x 50
04788
Torque nuts
DD380735.eps
20 M8 torque
nuts
Characteristics
Can be used to obtain the correct tightening torque (28 Nm) recommended by the manufacturer, without
using a torque wrench. Torque nuts may be used for all electrical connections.
Catalogue numbers
04759
Voltage tap-offs
DD380736.eps
20 Voltage
tap-offs M10
pour 2 clips 6.35
Characteristics
For small lugs (on low-current cables or measurement tap-offs), insert a conducting washer (cat. no. 04775)
between the busbar and the lug.
Catalogue numbers
04229
InA (A)
Connecting to Linergy LGYE
Connecting to Linergy LGY
0 to 630
Cable - Insulated flexible bars 25 mm Linergy connection hardware used 25 mm Linergy connection hardware used
800 to 1250
5 mm bars
25 mm Linergy connection hardware used 25 mm Linergy connection hardware used
1600 to 2500 5 mm or 10 mm bars
Use of the 2 studs flat plate
39 mm Linergy connection hardware used
3200 to 4000 10 mm bars
Use of the 3 studs flat plate
-
Connections on Linergy LGYE & LGY
Note:
Jointing between 2 busbars (horizontal/vertical or horizontal/horizontal) must be mandatory done with studs plates.