Linergy BS

Multi-stage busbars up to 630A

160 to 630 A copper busbars

DD381388-LIN.eps

160 A

250 A

400 A

630 A

Rated peak withstand current

(Ipk)

30 kÂ

40 kÂ

55 kÂ

55 kÂ

Rated insulation voltage

(Ui)

750 V AC

750 V AC

750 V AC

750 V AC

Rated short-time current

(Icw)

10 kA rms/1 s

13 kA rms/1 s

20 kA rms/1 s

25 kA rms/1 s

Thermal stress

(A².s)

1.000 x 10

8

1.690 x 10

8

4.000 x 10

8

6.250 x 10

8

Supply at incoming terminals

Connection by: 16 to 50 mm

2

flexible cables with crimped lugs.

Conductor cross-section

15 x 5 mm

20 x 5 mm

32 x 5 mm

32 x 8 mm

Installation

Flat copper busbar with threaded M6 holes every 25 mm all the way up.

Set of

4

Width (mm)

1000

1400

1000

1400

1000

1400

1000

1400

Catalogue numbers

04161

04171

04162

04172

04163

04173

To be made

04174

Insulating busbar support

(1)

DD381395-LIN.eps

Distance between

supports

depending on Icw/Ipk

(1)

y

10 kA rms/ 1 s / 30 k 450 mm

450 mm

450 mm

450 mm

y

13 kA rms/ 1 s / 40 k -

450 mm

450 mm

450 mm

y

15 kA rms/ 1 s / 40 k -

450 mm

450 mm

y

20 kA rms/ 1 s / 45 k -

-

300 mm

300 mm

y

25 kA rms/ 0.6 s / 55 k -

-

300 mm

-

y

25 kA rms/ 1 s / 55 k -

-

-

300 mm

Installation

Installation on functional uprights of duct (Prisma).

Screwed onto a solid or pre-slotted plate (450 x 200 mm fixing centres)

Catalogue numbers

04192

04192

04192

04192

IPxxB insulating protective shield

Dd383648.eps

Width

250 mm

Height

1500 mm

Composition

Fixing accessories supplied with support cat. no.

04192.

Catalogue numbers

04197

IEC 61439-1 & 2

Description

Multi-stage busbars are installed in a sheath W = 300 mm.

We strongly recommend dividing the current between 2 cubicles or enclosures

joined on either side.

All the connection points are easily accessible from the front.

The busbar orientation makes them easier to tighten and facilitates running the cables

between them.

The current can be 3-pole or 4-pole with ratings between 160Aand 630A.

2 lengths are available: 1000 and 1400 mm, which can be cut as required.

The number of supports depends on the installation maximum rated current.

Dd383648.eps

Distribution

Power busbars