B-25
Linergy BS
Multi-stage busbars up to 630A
160 to 630 A copper busbars
DD381388-LIN.eps
160 A
250 A
400 A
630 A
Rated peak withstand current
(Ipk)
30 kÂ
40 kÂ
55 kÂ
55 kÂ
Rated insulation voltage
(Ui)
750 V AC
750 V AC
750 V AC
750 V AC
Rated short-time current
(Icw)
10 kA rms/1 s
13 kA rms/1 s
20 kA rms/1 s
25 kA rms/1 s
Thermal stress
(A².s)
1.000 x 10
8
1.690 x 10
8
4.000 x 10
8
6.250 x 10
8
Supply at incoming terminals
Connection by: 16 to 50 mm
2
flexible cables with crimped lugs.
Conductor cross-section
15 x 5 mm
20 x 5 mm
32 x 5 mm
32 x 8 mm
Installation
Flat copper busbar with threaded M6 holes every 25 mm all the way up.
Set of
4
Width (mm)
1000
1400
1000
1400
1000
1400
1000
1400
Catalogue numbers
04161
04171
04162
04172
04163
04173
To be made
04174
Insulating busbar support
(1)
DD381395-LIN.eps
Distance between
supports
depending on Icw/Ipk
(1)
y
10 kA rms/ 1 s / 30 k 450 mm
450 mm
450 mm
450 mm
y
13 kA rms/ 1 s / 40 k -
450 mm
450 mm
450 mm
y
15 kA rms/ 1 s / 40 k -
450 mm
450 mm
y
20 kA rms/ 1 s / 45 k -
-
300 mm
300 mm
y
25 kA rms/ 0.6 s / 55 k -
-
300 mm
-
y
25 kA rms/ 1 s / 55 k -
-
-
300 mm
Installation
Installation on functional uprights of duct (Prisma).
Screwed onto a solid or pre-slotted plate (450 x 200 mm fixing centres)
Catalogue numbers
04192
04192
04192
04192
IPxxB insulating protective shield
Dd383648.eps
Width
250 mm
Height
1500 mm
Composition
Fixing accessories supplied with support cat. no.
04192.
Catalogue numbers
04197
IEC 61439-1 & 2
Description
Multi-stage busbars are installed in a sheath W = 300 mm.
We strongly recommend dividing the current between 2 cubicles or enclosures
joined on either side.
All the connection points are easily accessible from the front.
The busbar orientation makes them easier to tighten and facilitates running the cables
between them.
The current can be 3-pole or 4-pole with ratings between 160Aand 630A.
2 lengths are available: 1000 and 1400 mm, which can be cut as required.
The number of supports depends on the installation maximum rated current.
Dd383648.eps
Distribution
Power busbars