B-30
Linergy FC
Feeders for Compact NSX and INS
Distribution
Device feeders
PB502507-48_r.eps
PB502363-48_r.eps
Compact NSX100/250 & INS/INV250 - Toggle, fixed
PB502507-48_r.eps
Linergy FC with prefabricated connections by insulated flexible bars
Number of poles 3P
4P
Connection to
Linergy LGY busbars
Number of devices 4
3
Composition
Self-adhesive labels to mark the phases for connections to the busbars.
Cat. no.
04403
04404
Compact NSX100/250 - Rotary handle, motor mechanism, fixed
Compact NSX100/250 - All controls, withdrawable
(1)
Linergy FC with prefabricated braids
(1)
Number of poles 3P
4P
Connection to
Linergy BS, Linergy LGY or Linergy LGYE busbars
Number of devices 4
3
Composition
Self-adhesive labels to mark the phases for connections to the busbars.
Cat. no.
04405
04406
Compact NSX100/250 & INS/INV250 - All controls, fixed and withdrawable
PB502508-32_r.eps
Linergy FC without prefabricated connections
(1)
Number of poles 3P
4P
Connection to
Linergy BS, Linergy LGY or Linergy LGYE busbars
Number of devices 4
3
Composition
Self-adhesive labels to mark the phases for connections to the busbars.
Cat. no.
04407
(2)
04408
(2)
Implementation
DD381251-LIN-30.eps
DD381252-LIN-30.eps
DD381250-LIN.eps
Auxiliary wires running in the built-in trunking.
Phase marking on the front of the distribution block.
(1)
The connection of a Linergy FC distribution block using pre-wired connectors or insulated flexible bars is not compatible with Form 2 partitioning (04922).
In this case, use the form 2 restoration kit (04924).
(2)
For the connection, use insulated flexible bars, 32 x 8mm cat. no. 04753; Each connection must not be longer than 500 mm. This size is validated with
Schneider Electric insulated flexible bars.
IEC 61439-1 et 2
Description
Linergy FC is an insulated horizontal distribution block. It connects directly to the
mounting plate and can supply:
vv
three four-pole and four three-pole Compact NSX circuit breakers, whatever the
ratings (100, 160 or 250 A), the operating systems (toggle, rotary handle, motor
mechanism), whether fixed or plug-in, front or rear connection (the circuit breakers
must be equipped with long terminal shields downstream)
vv
three three-pole or four-pole Interpact INS switch-disconnectors, whatever the
ratings (100, 160 or 250 A), whether front or rear connection.
b
b
The design and small size blend perfectly with the devices.
b
b
It can be supplied by Linergy BS or Linergy LGY busbars positioned to the left or
right.
b
b
Fully insulated, Lynergy FC contributes to the safety of life and property.
Numerous and well distributed vents ensure natural convection and optimum cooling
of the conductors.
b
b
The circuit breakers can be easily connected from the front. It is simple to
interchange a device or to add a device in a reserve slot.
b
b
There are markings (N, L1, L2, L3) on the front and the sides for the phases.
b
b
The running of auxiliary cables between the devices and the corresponding
terminal blocks is also taken into account. Spacious trunking is built into the blocks
for the auxiliary wiring.