B-34
Quick distribution blocks
Number of poles
4P, upstream incoming
4P, downstream incoming
PB104500-6.eps
PB104499-6.eps
Rated operational current at 40°
(Ie)
63 A
63 A
Rated conditional short-circuit current of an
assembly
(Isc)
The reinforced breaking capacity due to cascading in
circuit breaker
combinations is maintained.
The worst-case situations have been tested.
The reinforced breaking capacity due to cascading in
circuit breaker
combinations is maintained.
The worst-case situations have been tested.
Rated peak withstand current
(Ipk)
-
-
Rated insulation voltage
(Ui)
500 V AC
500 V AC
Rated operational voltage
(Ue)
440 V AC
440 V AC
Rated impulse withstand voltage
(Uimp) 6 kV
6 kV
Rated short-time current
(Icw)
-
-
Thermal stress
(A².s) -
-
Rated operational frequency
50/60 Hz
50/60 Hz
Degree of protection
IPxxB
IPxxB
Incoming terminals
1 tunnel terminal 25²/phase
1 tunnel terminal 25²/phase
Total connection capacity, outgoing terminals
24 connections :
4 x 6²/phase
12 x 6²/neutre
24 connections :
4 x 6²/phase
12 x 6²/neutre
Dimensions (H x W x D)
96.5 x 72 x 62
8 x 9 mm pitch
96.5 x 72 x 62
8 x 9 mm pitch
Installation
Clipped onto a DIN rail
Clipped onto a DIN rail
Others
Standard for installation inside Prisma
IEC 61439-2
IEC 61439-2
Glow-wire 60695-2-11
960 °C
960 °C
Degree of pollution
3
3
Catalogue numbers
04040
04041
Accessories
Catalogue numbers
-
-
Linergy DX
Quick distribution blocks
Distribution
Distribution blocks
IEC 60947-7-1, CEI 61439-2
Description
bb
Downstream circuits are connected from the front, to spring terminals.
bb
Contact pressure automatically adapts to the size of the conductor.
bb
Contacts are insensitive to vibrations and thermal variations.
bb
Only one cable (flexible or rigid) can be inserted per terminal.
PB111415-19_r.eps
PB104499-7.eps