B-9

DD384555.EPS

H

C

F

G

H

H

C

F

G

H

H

C

F

G

H

Dd384518.EPS

Busbars presentation

Linergy LGYE 630 A to 4000 A

Horizontal and lateral busbars

Distribution

Main distribution

Horizontal busbars from 630 to 4000 A

Vertical busbars from 630 to 4000 A

Installation

The Linergy LGYE busbar can be installed

either at the top or the bottom of a frame.

>>

Size for 630 to 2500 A: 150 mm.

>>

Size for 3200 to 4000 A: 200 mm.

>>

The mounting technique is the same as

that for the Linergy BS busbar, sparing the

installer any constraints.

Installation

Flexibility for upgrading existing

switchboards

It is possible to mount the Linergy LGYE

busbar vertically for all ratings:

bb

630 to 2500 A, L = 150 mm

bb

3200 to 4000 A, L = 300 mm.

Busbar type

>>

Horizontal busbar:

bb

functionalized profiled busbar

L=2000mm

bb

for 630 to 2500 A busbars, a single strip is

incorporated over the entire length

bb

for 3200 to4000Abusbars, a double strip

is incorporated over the entire length.

Busbar type

>>

Vertical busbar:

bb

functionalized profiled busbar

L=2000mm to be re-cut to 1675mm for

connection with horizontal busbar from

1600 to 2500A.

bb

functionalized profiled busbar

L=2000mm to be re-cut to 1620 mm for

connection with horizontal busbar from

3200 to 4000A.

Warning:

this busbar does not allow the use of Prisma P