Contactors
Amplifier modules, electronic timer module, contactor monitoring device
2010
CA08103002Z-EN
www.eaton.com5/101
Amplifiermodules,electronic timermodule,contactormonitoringdevice
ETS4-VS3
DILM32-XTE
CMD(24VDC)
CMD(220-240VAC)
Contacts
Rated impulse withstand voltage
U
imp
V AC 6000
6000
8000
4000
Overvoltage category/degree of pollution
III/2
III/3
III/3
III/3
Rated insulation voltage
U
i
V AC 440
600
100
250
Rated operating voltage
U
e
V
440
AC
400
AC
24
DC
250
AC
Rated operational current
AC-15
220/240
V
I
e
A
2
3
–
–
380/415
V
I
e
A
2
–
–
–
DC-13
1)
DC-13 L/R ≦ 15 ms
Contacts in series:
1
24
V
A
2.6
1
–
–
1
60
V
A
1
0.2
–
–
1
110
V
A
0.6
0.2
–
–
1
220
V
A
0.2
0.1
–
–
DC-13 L/R ≦ 50 ms
Contacts in series:
1
24
V
A
2
1
–
–
1
60
V
A
0.6
0.2
–
–
1
110
V
A
0.08
0.2
–
–
1
220
V
A
0.08
0.1
–
–
DC-13 L/R ≦ 300 ms
Contacts in series:
1
24
V
A
0.6
1
–
–
1
60
V
A
0.2
0.2
–
–
1
110
V
A
0.08
0.2
–
–
1
220
V
A
0.03
0.1
–
–
Safe isolation according to EN 61140
Between coil and auxiliary contacts
V AC –
250
–
–
Between the auxiliary contacts
V AC –
250
–
–
Control circuit reliability
(
at U
e
= 24 V DC, U
min
= 17 V, I
min
= 5.4 mA)
Fault
probability
λ
<10
-8
,
< one failure in
100
million operations
–
–
–
Conventional thermal current
I
th
A
6
4
–
–
Component lifespan
AC-15
230
V, I
e
= 0.1 A
Switch
operations
x 10
6
7
–
–
–
230
V, I
e
= 1.2 A
Switch
operations
x 10
6
1
–
–
–
Short-circuit rating without welding
Short-circuit protection rating maximum
fuse
2)
500
V
A gG/gL –
4
2
2
500
V
A fast
4
–
–
–
Notes
1)
Switch-on and switch-off conditions based on DC-13, time constant as specified
2)
See transparent overlay "Fuses" for time/current characteristics (please enquire)
ETS-VS3, DILM, CMD