11/16

Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

11

Mains power protection

ESP M1R, M2R & M4R Series

Combined Type 1, 2 and 3 tested protector (to BS EN 61643) for use on mains

power distribution systems primarily to protect connected electronic

equipment from transient overvoltages on the mains supply, e.g. computer,

communications or control equipment. Remote display allows both display and

protector unit to be mounted in their optimum positions. For use at boundaries

up to LPZ

0

to protect against flashover (typically the main distribution

board location, with multiple metallic services entering) through to LPZ 3

to protect sensitive electronic equipment.

Installation

Installation of the protector unit is identical to the ESP M1,

M2 or M4. Position remote display, making sure that the

cable is long enough, is unimpeded within the cabinet, and

allows a minimum of 60 mm behind the panel front (for the

interconnection cable). For TT installations, contact Furse.

Accessories

ESP RLA-1

Spare 1 metre cable assembly

ESP RLA-2

Spare 2 metre cable assembly

ESP RLA-4

Spare 4 metre cable assembly

Full product range order codes can be

found on pages 17/8-17/9

NOTE:

For three phase applications where a remote display is unnecessary, use the respective ESP M1, M2 or M4 Series.

DIRTY

CLEAN

To load

From supply

Simple plug and

socket connection between

the protector unit and the

remote display

Features & benefits

–– The remote display means the protector can be mounted

close to the incoming feed or first way on the

distribution board and the display in an easily visible

position, e.g. on front of cabinet

–– Very low let-through voltage (enhanced protection to

IEC/BS EN 62305) between all sets of conductors (phase

to neutral, phase to earth, neutral to earth - Full Mode

protection)

–– Full Mode design capable of handling partial lightning

currents as well as allowing continual operation of

protected equipment

–– Repeated protection in lightning intense environments

–– Innovative multiple thermal disconnect technology for safe

disconnection from abnormal or faulty supplies

–– Remote display gives three way visual indication of

protection status

–– Plug-in cable connections between protector and display

enable easy connection (1 m cable supplied as standard)

–– Advanced pre-failure warning so you need never be

unprotected

–– Remote indication facility allows pre-failure warning to be

linked to a building management system, buzzer or light

–– Changeover active volt-free contact enables the protector

to be used to warn of phase loss (i.e. power failure,

blown fuses, etc)

–– Unique flashing warning of potentially fatal neutral to earth

supply faults (caused by incorrect earthing, wiring errors

or unbalanced conditions)

–– Robust steel housing (protector), and sturdy ABS

housing (display)

–– Base provides ultra-low inductance earth bond to

metal panels

–– Remote display comes with integral fixings and a panel

drilling template

Application

ESP M1R: main distribution board for buildings with multiple

metallic services (e.g. gas, water, telecoms) and sub-

distribution boards feeding sensitive equipment. ESP M2R:

main distribution board for buildings with Class III or IV LPS

fitted or exposed 3-ph power lines where no LPS is fitted.

ESP M4R: main distribution board for buildings with a Class I

Parallel connection of ESP 415

M1R to three phase star (4 wire

and earth) supplies (fuses not

shown for clarity)