Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

11/21

11

Mains power protection

ESP D/DS 10A & 32A Series (Single phase)

ESP D/DS 10A & 32A Series (Single phase) - Technical specification

ESP 120D-10A

ESP 120D-32A

ESP 240D-10A ESP 240D-32A ESP 277D-10A

ESP 277D-32A

Electrical specification

ESP 120DS-10A

ESP 120DS-32A ESP 240DS-10A

ESP 240DS-32A ESP 277DS-10A

ESP 277DS-32A

ABB order code

7TCA085460R0328 7TCA085460R0327 7TCA085460R0323 7TCA085460R0322 7TCA085460R0319 7TCA085460R0320

7TCA085460R0326 7TCA085460R0325 7TCA085460R0317 7TCA085460R0318 7TCA085460R0321 7TCA085460R0324

Nominal voltage - Phase-Neutral

U

o (RMS)

120 V

240 V

277 V

Maximum voltage - Phase-Neutral

U

c (RMS)

150 V

280 V

350 V

Temporary Overvoltage TOV

U

T

(1)

175 V

350 V

402 V

Short circuit withstand capability

10 kA/50 Hz

Working voltage (RMS)

90-150 V

200-280 V

232-350 V

Frequency range

47-63 Hz

Current rating (supply)

10 A or less

32 A or less

10 A or less

32 A or less

10 A or less

32 A or less

Max. back-up fuse (see installation instructions)

10 A

32 A

10 A

32 A

10 A

32 A

Leakage current (to earth)

Zero

Indicator circuit current

< 10 mA

Volt free contact (DS versions only):

(2)

Screw terminal

– Current rating

1 A

– Nominal voltage (RMS)

250 V

ESP 120D-10A

ESP 120D-32A

ESP 240D-10A ESP 240D-32A ESP 277D-10A

ESP 277D-32A

Transient specification

ESP 120DS-10A

ESP 120DS-32A ESP 240DS-10A

ESP 240DS-32A ESP 277DS-10A

ESP 277DS-32A

Type 1 (BS EN/EN), Class I (IEC)

Nominal discharge current 8/20 μs (per mode)

I

n

20 kA

Let-through voltage

U

p at

I

n

< 1 kV

< 1.3 kV

< 1.4 kV

Impulse discharge current 10/350 μs

I

imp (L-N/E, N-E)

(4)

4 kA, 12.5 kA

Let-through voltage

U

p at

I

imp

(3)

< 1 kV

< 1.2 kV

< 1.3 kV

Total discharge current (total to earth)

I

total

(4,5)

6.25 kA

Type 2 (BS EN/EN), Class II (IEC)

Nominal discharge current 8/20 μs (per mode)

I

n

20 kA

Let-through voltage

U

p at

I

n

< 1 kV

< 1.3 kV

< 1.4 kV

Maximum discharge current

I

max (L-N/E, N-E)

(4)

40 kA, 40 kA

Type 3 (BS EN/EN), Class III (IEC)

Let-through voltage at

U

oc of 6 kV 1.2/50 μs and

Is

c of 3 kA 8/20 μs (per mode)

(3,6)

400 V

600 V

680 V

ESP 120D-10A

ESP 120D-32A

ESP 240D-10A ESP 240D-32A ESP 277D-10A

ESP 277D-32A

Mechanical specification

ESP 120DS-10A

ESP 120DS-32A ESP 240DS-10A

ESP 240DS-32A ESP 277DS-10A

ESP 277DS-32A

Temperature range

-40 to +80 °C

Connection type

Screw terminal - maximum torque 0.8 Nm

(7)

Conductor size (stranded)

6 mm

2

Earth connection

Screw terminal - maximum torque 0.8 Nm

(7)

Volt free contact (DS versions only)

Connect via screw terminal with conductor up to 1.5 mm

2

(stranded) - maximum torque 0.25 Nm

(7)

Degree of protection (IEC 60529)

IP20

Case material

FR Polymer UL-94 V-0

Weight: – Unit

0.23 kg

– Packaged

0.25 kg

Dimensions to DIN 43880 - HxDxW

(8)

90 mm x 75 mm x 36 mm (2TE)

*To enclose the products to IP65, fit within a WDX D4, available from Furse

(1)

Temporary Overvoltage rating is for a maximum duration of

5 seconds tested to BS EN/EN/IEC 61643

(2)

Minimum permissable load is 5 V DC, 10 mA to ensure

reliable operation

(3)

The maximum transient voltage let-through of the protector

throughout the test (±10%)

(4)

The electrical system, external to the unit, may constrain the

actual current rating achieved in a particular installation

36 mm

90mm

45mm

50 mm 25 mm

Standard

depth

75 mm

(5)

Rating is considered as the current capability of the protector

for equipotential bonding near the service entrance

(6)

Combination wave test within IEC/BS EN 61643,

IEEE C62.41-2002 Location Cats C1 & B3, SS 555:2010,

AS/NZS 1768-2007, UL 1449 mains wire-in

(7)

Torque should typically be 50% to 75% of the maximum value

(8)

The remote signal contact (removable) adds 10 mm to height