ESP MC Series - Technical specification

Electrical specification - mains

ESP MC

ESP MC/TN/RJ11 ESP MC/Cat-5e

ABB order code

7TCA085430R0003 7TCA085430R0005 7TCA085430R0004

Nominal voltage - Phase-Neutral

U

o (RMS)

220/230/240 V

Maximum voltage - Phase-Neutral

U

c (RMS)

280 V

Frequency range

47-63 Hz

Current rating (supply)

13 A

Leakage current (to earth)

< 0.5 mA

Electrical specification - telecom/data

ESP MC

ESP MC/TN/RJ11 ESP MC/Cat-5e

Nominal voltage

296 V

5 V

Maximum working voltage

U

c

(1)

296 V

5 V

(2)

Current rating (signal)

300 mA

300 mA

In-line resistance (per line ±10%)

4.4 Ω

1 Ω

Bandwidth (-3 dB 50 Ω system)

20 MHz

Maximum data rate

100 Mbps

Transient specification - mains

ESP MC

ESP MC/TN/RJ11 ESP MC/Cat-5e

Type 2 (BS EN/EN), Class II (IEC)

Nominal discharge current 8/20 μs (per mode)

I

n

5 kA

Let-through voltage

U

p at

I

n

(3)

850 V

Maximum discharge current

I

max (per mode)

(4)

10 kA

Type 3 (BS EN/EN), Class III (IEC)

Let-through voltage at

U

oc of 6 kV 1.2/50 μs and

I

sc of 3 kA 8/20 μs (per mode)

(3,5)

680 V

Let-through voltage at

U

oc of 6 kV 1.2/50 μs and

Is

c of 500 A 8/20 (per mode)

(3,5)

555 V

Transient specification - telecom/data

ESP MC

ESP MC/TN/RJ11 ESP MC/Cat-5e

Let-through voltage (all conductors)

(6)

U

p

C2 test 4 kV 1.2/50 μs, 2 kA 8/20 μs to

BS EN/EN/IEC 61643-21 - line to line / line to earth

390 V/390 V

120 V/700 V

(8)

C1 test 1 kV, 1.2/50 μs, 0.5 kA 8/20 μs to

BS EN/EN/IEC 61643-21 - line to line / line to earth –

395 V/395 V

74 V/600 V

(8)

B2 test 4 kV 10/700 μs to

BS EN/EN/IEC 61643-21 - line to line / line to earth –

295 V/295 V

21 V/550 V

(8)

5 kV, 10/700 μs

(7)

- line to line / line to earth

300 V/300 V

25 V/600 V

(8)

Maximum surge current

(9)

D1 test 10/350 μs to BS EN/EN/IEC 61643-21

1 kA

1 kA

8/20 μs to ITU (formerly CCITT), BS 6651:1999 Appendix C –

10 kA

10 kA

Mechnical specification

ESP MC

ESP MC/TN/RJ11 ESP MC/Cat-5e

Temperature range

-40 °C to +80 ºC

Connection type

Via British style three square pin plug and socket to BS 1363

Conductor size (solid)

RJ11

RJ45

Earth connection

Via plug and socket

Case material

Steel

Weight: – Unit

1.70 kg

1.75 kg

1.75 kg

– Packaged

1.75 kg

1.8 kg

1.8 kg

(1)

Maximum working voltage (DC or AC peak) of

telecom/data protection measured at <10 μA leakage for

ESP MC/TN/RJ11 and 1 mA for ESP MC/Cat-5e

(2)

Maximum working voltage is 5 V for data pairs 1/2 & 3/6

(3)

The maximum transient voltage let-through of the protector

throughout the test (±10%), phase to neutral, phase to

earth and neutral to earth

(4)

The electrical system, external to the unit, may constrain the

actual current rating achieved in a particular installation

(5)

Combination wave test within IEC/BS EN 61643,

IEEE C62.41-2002 Location Cats C1 & B3, SS 555:2010,

AS/NZS 1768-2007, UL 1449 mains wire-in

(6)

The maximum transient voltage let-through the protector

throughout the test (±10%), line to line & line to earth.

Response time < 10 ns

(7)

Test to IEC/BS EN 61643, IEC 61000-4-5:2006, ITU-T

(formerly CCITT) K.20, K.21 and K.45,Telcordia

GR-1089-CORE, Issue 2:2002,ANSI TIA/EIA/IS-968-A:2002

(formerly FCC Part 68)

(8)

The interfaces used in Cat-5/5e systems incorporate an isolation

transformer that inherently provides an inbuilt immunity

to transients between line and earth of 1,500 Volts or more

(9)

The installation and connectors external to the protector

may limit the capability of the protector

Mains power protection

ESP MC Series