Table of Contents Table of Contents
Previous Page  220 / 336 Next Page
Information
Show Menu
Previous Page 220 / 336 Next Page
Page Background

11/20

Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

11

Mains power protection

ESP D/DS 10A & 32A Series (Single phase)

NOTE:

If your supply is fused at more than 32 Amps the ESP 120 M1, ESP 240 M1 or ESP 277 M1 are suitable.

Combined Type 1, 2 and 3 tested protector (to BS EN 61643) for use on low

current (up to 10 or 32 A ) single phase systems to protect connected electronic

equipment from transient overvoltages on the mains supply, e.g. fire/intruder

alarm panels. Available for 90-150 Volts, 200-280 Volts and 232-350 Volts

supplies. For use at boundary LPZ 0 through to LPZ 3 boundaries to protect

sensitive electronic equipment.

Features & benefits

–– Very low let-through voltage (enhanced protection to

IEC/BS EN 62305) between all sets of conductors (phase

to neutral, phase to earth, neutral to earth - Full Mode

protection)

–– Repeated protection in lightning intense environments

–– Compact space saving DIN housing for easy incorporation

in the protected system

–– Innovative multiple thermal disconnect technology for safe

disconnection from faulty or abnormal supplies (without

compromising protective performance)

–– Three way visual indication of protection status and

advanced pre-failure warning so you need never

be unprotected

–– Advanced status (DS) version has remote indication facility

to a BMS via an active changeover volt-free contact to

show pre-failure warnings and potential phase loss

(i.e. power failure, blown fuses etc), and a flashing warning

of potentially fatal neutral to earth supply volts

Installation

Connect in-line with the power supply usually either

within the equipment panel (or for CCTV cameras, in an

enclosure close by), or on the fused connection that

supplies equipment.

To protect equipment inside a building from transients

entering on an outgoing feed (e.g. to CCTV cameras or to

site lighting) the protector should be installed as

close to where the cable leaves the building as possible.

Protectors should be installed either within an existing

cabinet/cubicle or in a separate enclosure.

Accessories

Weatherproof enclosure:

WBX D4

Full product range order codes can be found on pages 17/8-17/9

Connect in-line on supplies fused up to 10 A (ESP 120D-10A,

ESP 120DS-10A, ESP 240D-10A, ESP 240DS-10A, ESP 277D-10A or

ESP 277DS-10A) or 32 A (ESP 120D-32A, ESP 120DS-32A,

ESP 240D-32A, ESP 240DS-32A, ESP 277D-32A or ESP 277DS-32A)

L N

L N

N L

N L

L N

L N

N L

N L

11COM

14N/O

12N/C

L

!

GREEN

FULLPROTECTION

GREEN&RED

REDUCED

PROTECTION

(replaceunit)

RED

NOPROTECTION

WARNING: If lit /

flashingdisconnect

unit&checkNeutral

toEarthvoltage

STATUS INDICATION

ESP 240DS-32A

LINE

CLEAN

LINE

CLEAN

To:

BMS

PLC

Buzzer

Application

Use these protectors on low current mains power supplies,

e.g. CCTV cameras, alarm panels, industrial battery chargers

and telemetry equipment.