Mains power protection
ESP DC Series
Combined Type 2 and 3 tested protector (to BS EN 61643) for use on DC systems
to protect connected electronic equipment from transient overvoltages on the
mains supply, e.g. control equipment. Available for 12, 24, 36 and 48 V DC systems.
For use at boundaries LPZ 1 through to LPZ 3 to protect sensitive
electronic equipment.
Installation
Install in parallel, within the power distribution board or
directly on the supply feeding the equipment. At distribution
boards, the protector can be installed either on the load side
of the incoming isolator, or on the closest outgoing way to the
incoming supply. Connect, with very short connecting leads,
to positive, negative and earth.
Accessories
Weatherproof enclosure:
WBX 3
Full product range order codes can be found on pages 17/8-17/9
NOTE:
For low current applications, the ESP H Series (4 A), ESP E Series (1.25 A) or ESP D Series (300 mA) protectors may be suitable. For protection of
photovoltaic (PV) systems up to 1000 Vdc, see our ESP PV Series.
Parallel connection of ESP 48 DC
DIRTY
CLEAN
To
load
From
supply
Application
Use on DC power distribution systems to protect connected
electronic equipment from transient overvoltages on the DC
Features & benefits
–– Low let-through voltage (enhanced protection to
IEC/BS EN 62305) between all sets of conductors (positive
to negative, positive to earth and negative to earth -
Full Mode protection) allowing continuous operation of
equipment
–– Repeated protection in lightning intense environments
–– Visual indication of protector status
–– Advanced pre-failure warning so you need never
be unprotected
–– Remote indication facility allows pre-failure warning to be
linked to a building management system, buzzer or light
–– Robust steel housing
–– Simple parallel connection
–– Base provides ultra-low inductance earth bond to
metal panels
–– Compact size for installation in the power distribution board