Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

11/13

11

ESP M2/M4 Series - Technical specification

Electrical specification

ESP 415 M2

ESP 415 M4

ESP 480 M2

ESP 480 M4

ABB order code

7TCA085460R0119 7TCA085460R0124 7TCA085460R0138 7TCA085460R0140

Nominal voltage - Phase-Neutral

U

o (RMS)

240 V

240 V

277 V

277 V

Maximum voltage - Phase-Neutral

U

c (RMS)

280 V

280 V

350 V

350 V

Temporary Overvoltage TOV

U

T

(1)

350 V

350 V

402 V

402 V

Short circuit withstand capability

25 kA/50 Hz

Working voltage (RMS)

346-484 V

346-484 V

402-600 V

402-600 V

Frequency range

47-63 Hz

Max. back-up fuse (see installation instructions)

≤ 200 A

≤ 315 A

≤ 200 A

≤ 315 A

Leakage current (to earth)

< 500 μA

< 1000 μA

< 500 μA

< 1000 μA

Indicator circuit current

< 20 mA

< 40 mA

< 20 mA

< 40 mA

Volt free contact:

(2)

Screw terminal

– Current rating

1 A

– Nominal voltage (RMS)

250 V

Transient specification

ESP 415 M2

ESP 415 M4

ESP 480 M2

ESP 480 M4

Type 1 (BS EN/EN), Class I (IEC)

Nominal discharge current 8/20 μs (per mode)

I

n

20 kA

25 kA

20 kA

25 kA

Let-through voltage

U

p at

I

n

(3)

< 1.3 kV

< 1.4 kV

< 1.4 kV

< 1.5 kV

Impulse discharge current 10/350 μs

I

imp (to earth)

(4)

12.5 kA

25 kA

12.5 kA

25 kA

Let-through voltage

U

p at

I

imp

(2)

< 1.2 kV

< 1.3 kV

< 1.4 kV

< 1.5 kV

Total discharge current 10/350 µs

I

total (total to earth)

(4,5)

50 kA

100 kA

50 kA

100 kA

Type 2 (BS EN/EN), Class II (IEC)

Nominal discharge current 8/20 μs (per mode)

I

n

20 kA

25 kA

20 kA

25 kA

Let-through voltage

U

p at

I

n

(3)

< 1.3 kV

< 1.4 kV

< 1.4 kV

< 1.5 kV

Maximum discharge current

I

max (L/N-PE, L-N)

(4)

80 kA, 40 kA 150 kA, 40 kA 80 kA, 40 kA 150 kA, 40 kA

Type 3 (BS EN/EN), Class III (IEC)

Let-through voltage at

U

oc of 6 kV 1.2/50 μs and

Is

c of 3 kA 8/20 μs (per mode)

(3,6)

600 V

600 V

680 V

680 V

Mechanical specification

ESP 415 M2

ESP 415 M4

ESP 480 M2

ESP 480 M4

Temperature range

-40 to +80 °C

Connection type

Screw terminal - maximum torque 2.5 Nm (ESP M2), 5.6 Nm (ESP M4)

Conductor size (stranded)

25 mm

2

50 mm

2

25 mm

2

50 mm

2

Earth connection

Screw terminal - maximum torque 2.5 Nm (ESP M2), 5.6 Nm (ESP M4)

Volt free contact

Connect via screw terminal with conductor up to 2.5 mm

2

(stranded) - maximum torque 0.25 Nm

Degree of protection (IEC 60529)

IP20

Case material

Steel

Weight: – Unit

2.35 kg

3.9 kg

2.35 kg

3.9 kg

– Packaged

2.5 kg

4.2 kg

2.5 kg

4.2 kg

Dimensions

226 mm x 204 mm 226 mm x 204 mm 226 mm x 204 mm 226 mm x 204 mm

x 78 mm

x 125 mm

x 78 mm

x 125 mm

(1)

Temporary Overvoltage rating is for a maximum duration of

5 seconds tested to BS EN/EN/IEC 61643

(2)

Minimum permissable load is 5 V DC, 10 mA to ensure

reliable operation

(3)

The maximum transient voltage let-through of the protector

throughout the test (±10%), phase to neutral, phase to

earth and neutral to earth

(4)

The electrical system, external to the unit, may constrain the

actual current rating achieved in a particular installation

(5)

Rating is considered as the current capability of the protector

for equipotential bonding near the service entrance

(6)

Combination wave test within IEC/BS EN 61643,

IEEE C62.41-2002 Location Cats C1 & B3, SS 555:2010,

AS/NZS 1768-2007, UL 1449 mains wire-in

ESP XXX M2/M4

M5 Clearance

Note: The unit

takes up 25 mm

of the length of

the fixing screw

Depth:

78 mm (ESP M2)

125 mm (ESP M4)

226 mm

176 mm

204 mm

186.5 mm

Mains power protection

ESP M2/M4 Series