Total Solution to Earthing & Lightning Protection |
9AKK106354A3360
11/13
11
ESP M2/M4 Series - Technical specification
Electrical specification
ESP 415 M2
ESP 415 M4
ESP 480 M2
ESP 480 M4
ABB order code
7TCA085460R0119 7TCA085460R0124 7TCA085460R0138 7TCA085460R0140
Nominal voltage - Phase-Neutral
U
o (RMS)
240 V
240 V
277 V
277 V
Maximum voltage - Phase-Neutral
U
c (RMS)
280 V
280 V
350 V
350 V
Temporary Overvoltage TOV
U
T
(1)
350 V
350 V
402 V
402 V
Short circuit withstand capability
25 kA/50 Hz
Working voltage (RMS)
346-484 V
346-484 V
402-600 V
402-600 V
Frequency range
47-63 Hz
Max. back-up fuse (see installation instructions)
≤ 200 A
≤ 315 A
≤ 200 A
≤ 315 A
Leakage current (to earth)
< 500 μA
< 1000 μA
< 500 μA
< 1000 μA
Indicator circuit current
< 20 mA
< 40 mA
< 20 mA
< 40 mA
Volt free contact:
(2)
Screw terminal
– Current rating
1 A
– Nominal voltage (RMS)
250 V
Transient specification
ESP 415 M2
ESP 415 M4
ESP 480 M2
ESP 480 M4
Type 1 (BS EN/EN), Class I (IEC)
Nominal discharge current 8/20 μs (per mode)
I
n
20 kA
25 kA
20 kA
25 kA
Let-through voltage
U
p at
I
n
(3)
< 1.3 kV
< 1.4 kV
< 1.4 kV
< 1.5 kV
Impulse discharge current 10/350 μs
I
imp (to earth)
(4)
12.5 kA
25 kA
12.5 kA
25 kA
Let-through voltage
U
p at
I
imp
(2)
< 1.2 kV
< 1.3 kV
< 1.4 kV
< 1.5 kV
Total discharge current 10/350 µs
I
total (total to earth)
(4,5)
50 kA
100 kA
50 kA
100 kA
Type 2 (BS EN/EN), Class II (IEC)
Nominal discharge current 8/20 μs (per mode)
I
n
20 kA
25 kA
20 kA
25 kA
Let-through voltage
U
p at
I
n
(3)
< 1.3 kV
< 1.4 kV
< 1.4 kV
< 1.5 kV
Maximum discharge current
I
max (L/N-PE, L-N)
(4)
80 kA, 40 kA 150 kA, 40 kA 80 kA, 40 kA 150 kA, 40 kA
Type 3 (BS EN/EN), Class III (IEC)
Let-through voltage at
U
oc of 6 kV 1.2/50 μs and
Is
c of 3 kA 8/20 μs (per mode)
(3,6)
600 V
600 V
680 V
680 V
Mechanical specification
ESP 415 M2
ESP 415 M4
ESP 480 M2
ESP 480 M4
Temperature range
-40 to +80 °C
Connection type
Screw terminal - maximum torque 2.5 Nm (ESP M2), 5.6 Nm (ESP M4)
Conductor size (stranded)
25 mm
2
50 mm
2
25 mm
2
50 mm
2
Earth connection
Screw terminal - maximum torque 2.5 Nm (ESP M2), 5.6 Nm (ESP M4)
Volt free contact
Connect via screw terminal with conductor up to 2.5 mm
2
(stranded) - maximum torque 0.25 Nm
Degree of protection (IEC 60529)
IP20
Case material
Steel
Weight: – Unit
2.35 kg
3.9 kg
2.35 kg
3.9 kg
– Packaged
2.5 kg
4.2 kg
2.5 kg
4.2 kg
Dimensions
226 mm x 204 mm 226 mm x 204 mm 226 mm x 204 mm 226 mm x 204 mm
x 78 mm
x 125 mm
x 78 mm
x 125 mm
(1)
Temporary Overvoltage rating is for a maximum duration of
5 seconds tested to BS EN/EN/IEC 61643
(2)
Minimum permissable load is 5 V DC, 10 mA to ensure
reliable operation
(3)
The maximum transient voltage let-through of the protector
throughout the test (±10%), phase to neutral, phase to
earth and neutral to earth
(4)
The electrical system, external to the unit, may constrain the
actual current rating achieved in a particular installation
(5)
Rating is considered as the current capability of the protector
for equipotential bonding near the service entrance
(6)
Combination wave test within IEC/BS EN 61643,
IEEE C62.41-2002 Location Cats C1 & B3, SS 555:2010,
AS/NZS 1768-2007, UL 1449 mains wire-in
ESP XXX M2/M4
M5 Clearance
Note: The unit
takes up 25 mm
of the length of
the fixing screw
Depth:
78 mm (ESP M2)
125 mm (ESP M4)
226 mm
176 mm
204 mm
186.5 mm
Mains power protection
ESP M2/M4 Series