Mains power protection
ESP D1 Series (Single phase)
ESP D1 Series (Single phase) - Technical specification
Electrical specification
ESP 120 D1
ESP 240 D1
ESP 277 D1
ABB order code
7TCA085460R0069 7TCA085460R0086 7TCA085460R0096
Nominal voltage - Phase-Neutral
U
o (RMS)
120 V
240 V
277 V
Maximum voltage - Phase-Neutral
U
c (RMS)
150 V
280 V
350 V
Temporary Overvoltage TOV
U
T
(1)
175 V
350 V
402 V
Short circuit withstand capability
25 kA/50 Hz
Working voltage (RMS)
156-260 V
346-484 V
402-600 V
Frequency range
47-63 Hz
Max. back-up fuse (see installation instructions)
≤ 125 A
Leakage current (to earth)
< 250 μA
Indicator circuit current
< 10 mA
Volt free contact:
(2)
Screw terminal
– Current rating
1 A
– Nominal voltage (RMS)
250 V
Transient specification
ESP 120 D1
ESP 240 D1
ESP 277 D1
Type 1 (BS EN/EN), Class I (IEC)
Nominal discharge current 8/20 μs (per mode)
I
n
20 kA
Let-through voltage
U
p at
I
n
< 1 kV
< 1.3 kV
< 1.4 kV
Impulse discharge current 10/350 μs
I
imp (to earth)
(5)
4 kA
Let-through voltage
U
p at
I
imp
< 1 kV
< 1.2 kV
< 1.3 kV
Total discharge current 10/350 μs
I
total (total to earth)
(4,5)
8 kA
Type 2 (BS EN/EN), Class II (IEC)
Nominal discharge current 8/20 μs (per mode)
I
n
20 kA
Let-through voltage
U
p at
I
n
< 1 kV
< 1.3 kV
< 1.4 kV
Maximum discharge current
I
max (L/N-E, L-N)
(4)
40 kA, 40 kA
Type 3 (BS EN/EN), Class III (IEC)
Let-through voltage at
U
oc of 6 kV 1.2/50 μs and
Is
c of 3 kA 8/20 μs (per mode)
(3,6)
400 V
600 V
680 V
Mechanical specification
ESP 120 D1
ESP 240 D1
ESP 277 D1
Temperature range
-40 to +80 °C
Connection type
Screw terminal - maximum torque 4.5Nm
Conductor size (stranded)
25 mm
2
Earth connection
Screw terminal - maximum torque 4.5Nm
Volt free contact
Connect via screw terminal with conductor up to 1.5 mm
2
(stranded) - maximum torque 0.25 Nm
Degree of protection (IEC 60529)
IP20
Case material
FR Polymer UL-94 V-0
Weight: – Unit
0.4 kg
– Packaged
0.5 kg
Dimensions to DIN 43880 - HxDxW
(7)
90 mm x 88 mm x 72 mm (4TE)
(1)
Temporary Overvoltage rating is for a maximum duration of
5 seconds tested to BS EN/EN/IEC 61643
(2)
Minimum permissable load is 5 V DC, 10 mA to ensure
reliable operation
(3)
The maximum transient voltage let-through of the protector
throughout the test (±10%), phase to neutral, phase to
earth and neutral to earth
(4)
Rating is considered as the current capability of the protector
for equipotential bonding near the service entrance
(5)
The electrical system, external to the unit, may constrain the
actual current rating achieved in a particular installation
(6)
Combination wave test within IEC/BS EN 61643,
IEEE C62.41-2002 Location Cats C1 & B3, SS 555:2010,
AS/NZS 1768-2007, UL 1449 mains wire-in
(7)
The remote signal contact (removable) adds 10 mm to height
72 mm
90 mm
45 mm
50 mm 38 mm
Standard
depth
88 mm