ESP 240/XXX Series - Technical specification

Electrical specification

ESP 240/I/TNS

ESP 240/III/TNS ESP 240/I/TNC

ESP 240/III/TNC ESP 240/I/TT

ESP 240/III/TT

ABB order code

7TCA085460R0019 7TCA085460R0022 7TCA085460R0018 7TCA085460R0021 7TCA085460R0020 7TCA085460R0023

Nominal voltage - Phase-Neutral

U

o (RMS)

240 V

Maximum voltage - Phase-Neutral

U

c (RMS/DC)

320 V/420 V

Temporary Overvoltage TOV

U

T

(1)

350 V

Short circuit withstand capability

25 kA/50 Hz

Frequency range

47-63 Hz

Max. back-up fuse (see installation instructions)

250 A

Leakage current (to earth)

≤ 250 A

< 2.5 mA

< 2.5 mA

< 2.5 mA

0

0

Volt free contact:

Screw terminal

– Current rating

0.5 A

– Nominal voltage (RMS)

250 V

Transient specification

ESP 240/I/TNS

ESP 240/III/TNS ESP 240/I/TNC

ESP 240/III/TNC ESP 240/I/TT

ESP 240/III/TT

Type 1 (BS EN/EN), Class I (IEC)

Nominal discharge current 8/20 μs (per mode)

I

n

25 kA

25 kA

25 kA

25 kA

25 kA/100 kA (N-E) 25 kA/50 kA (N-E)

Let-through voltage

U

p at

I

n

(2)

< 1.4 kV

< 1.4 kV

< 1.4 kV

< 1.4 kV

< 1.4 kV

< 1.4 kV

Impulse discharge current 10/350 μs

I

imp (per mode)

(2)

50 kA

25 kA

50 kA

25 kA

50 kA/100 kA (N-E) 25 kA/50 kA (N-E)

Let-through voltage

U

p at

I

imp

(2)

< 1.2 kV

< 1.2 kV

< 1.2 kV

< 1.2 kV

< 1.2 kV

< 1.2 kV

Let-through voltage

U

p at 1.2/50 μs (N-E, TT system)

< 1.2 kV

< 1.2 kV

Type 2 (BS EN/EN), Class II (IEC)

Nominal discharge current 8/20 μs (per mode)

I

n

25 kA

25 kA

25 kA

25 kA

25 kA/100 kA (N-E) 25 kA/50 kA (N-E)

Let-through voltage

U

p at

I

n

(2)

< 1.4 kV

< 1.4 kV

< 1.4 kV

< 1.4 kV

< 1.4 kV

< 1.4 kV

Maximum discharge current Imax (per mode)

(3)

100 kA

100 kA

100 kA

100 kA

100 kA/160 kA (N-E) 100 kA/100 kA (N-E)

Mechanical specification

ESP 240/I/TNS

ESP 240/III/TNS ESP 240/I/TNC

ESP 240/III/TNC ESP 240/I/TT

ESP 240/III/TT

Temperature range

-40 to +80 °C

Connection type

Screw terminal - maximum torque 4.5 Nm

Conductor size (stranded)

25 mm

2

Earth connection

Screw terminal - maximum torque 4.5 Nm

Degree of protection (IEC 60529)

IP20

Volt free contact

Connect via screw terminal with conductor up to 1.5 mm

2

(stranded) - maximum torque 0.25 Nm

Case material

FR Polymer UL-94 V-0

Mounting

Indoor, 35 mm top hat DIN rail

Weight: – Unit

0.84 kg

0.44 kg

0.44 kg

0.29 kg

0.68 kg

0.44 kg

– Packaged

0.94 kg

0.54 kg

0.54 kg

0.39 kg

0.78 kg

0.54 kg

Dimensions to DIN 43880 - HxDxW

(4)

90 mm x 68 mm 90 mm x 68 mm 90 mm x 68 mm 90 mm x 68 mm 90 mm x 68 mm 90 mm x 68 mm

x 72 mm (4TE)

x 36 mm (2TE)

x 36 mm (2TE)

x 36 mm (2TE)

x 72 mm (4TE)

x 54 mm (3TE)

72 mm

ESP 240/I/TNS

ESP 240/I/TT

54 mm

ESP 240/III/TT

36 mm

90 mm

ESP 240/III/TNS

ESP240/I/TNC

ESP240/III/TNC

45 mm

51 mm

Standard

depth

68 mm

(1)

Temporary Overvoltage rating is for a maximum duration of

5 seconds tested to BS EN/EN/IEC 61643

(2)

The maximum transient voltage let-through of the protector

throughout the test, phase to earth and neutral to earth

(3)

The electrical system, external to the unit, may constrain the

actual current rating achieved in a particular installation

(4)

The remote signal contact (removable) adds 10 mm to height

Mains power protection

ESP 240/XXX Series