Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

11/7

11

ESP 415/XXX Series - Technical specification

Electrical specification

ESP 415/I/TNS

ESP 415/III/TNS ESP 415/I/TNC

ESP 415/III/TNC ESP 415/I/TT

ESP 415/III/TT

ABB order code

7TCA085460R0101 7TCA085460R0103 7TCA085460R0024 7TCA085460R0025 7TCA085460R0102 7TCA085460R0026

Nominal voltage - Phase-Neutral

U

o (RMS)

240 V

Maximum voltage - Phase-Neutral

U

c (RMS/DC)

320 V/420 V

Temporary Overvoltage TOV

U

T

(1)

350 V

Short circuit withstand capability

25 kA/50 Hz

Frequency range

47-63 Hz

Max. back-up fuse (see installation instructions)

250 A

Leakage current (to earth)

≤ 250 A

< 2.5 mA

< 2.5 mA

< 2.5 mA

0

0

Volt free contact:

(2)

Screw terminal

– Current rating

0.5 A

– Nominal voltage (RMS)

250 V

Transient specification

ESP 415/I/TNS

ESP 415/III/TNS ESP 415/I/TNC

ESP 415/III/TNC ESP 415/I/TT

ESP 415/III/TT

Type 1 (BS EN/EN), Class I (IEC)

Nominal discharge current 8/20 μs (per mode)

I

n

25 kA

20 kA

25 kA

20 kA

25 kA/100 kA (N-E) 20 kA/50 kA (N-E)

Let-through voltage

U

p at

I

n

(2)

< 1.4 kV

< 1.5 kV

< 1.4 kV

< 1.5 kV

< 1.4 kV

< 1.5 kV

Impulse discharge current 10/350 μs

I

imp (per mode)

(3)

25 kA

12.5 kA

25 kA

12.5 kA

25 kA/100 kA (N-E) 12.5 kA/50 kA (N-E)

Let-through voltage

U

p at

I

imp

(2)

< 1.3 kV

< 1.2 kV

< 1.3 kV

< 1.2 kV

< 1.3 kV

< 1.2 kV

Let-through voltage

U

p at 1.2/50 μs (N-E, TT system)

< 1.2 kV

< 1.2 kV

Type 2 (BS EN/EN), Class II (IEC)

Nominal discharge current 8/20 μs (per mode)

I

n

25 kA

20 kA

25 kA

20 kA

25 kA/100 kA (N-E) 20 kA/50 kA (N-E)

Let-through voltage

U

p at

I

n

(2)

< 1.4 kV

< 1.5 kV

< 1.4 kV

< 1.5 kV

< 1.4 kV

< 1.5 kV

Maximum discharge current Imax (per mode)

(3)

100 kA

50 kA

100 kA

50 kA

100 kA/160 kA (N-E) 50 kA/200 kA (N-E)

Mechanical specification

ESP 415/I/TNS

ESP 415/III/TNS ESP 415/I/TNC

ESP 415/III/TNC ESP 415/I/TT

ESP 415/III/TT

Temperature range

-40 to +80 °C

Connection type

Screw terminal

Conductor size (stranded)

25 mm

2

Earth connection

Screw terminal

Volt free contact

Connect via screw terminal with conductor up to 1.5 mm

2

(stranded)

Degree of protection (IEC 60529)

IP20

Case material

FR Polymer UL-94 V-0

Mounting

Indoor, 35 mm top hat DIN rail

Weight: – Unit

0.84 kg

0.59 kg

0.64 kg

0.44 kg

0.9 kg

0.67 kg

– Packaged

0.94 kg

0.69 kg

0.74 kg

0.54 kg

1.0 kg

0.77 kg

Dimensions to DIN 43880 - HxDxW

(4)

90 mm x 68 mm 90 mm x 68 mm 90 mm x 68 mm 90 mm x 68 mm 90 mm x 68 mm 90 mm x 68 mm

x 72 mm (4TE)

x 72 mm (4TE)

x 54 mm (3TE)

x 54 mm (3TE)

x 90 mm (5TE)

x 72 mm (4TE)

72 mm

ESP 415/I/TNS

ESP 415/III/TNS

90 mm

ESP 415/I/TT

ESP 415/III/TT

54 mm

90 mm

ESP 415/I/TNC

ESP 415/III/TNC

45 mm

51 mm

Standard

depth

68 mm

Mains power protection

ESP 415/XXX Series

(1)

Temporary Overvoltage rating is for a maximum duration of

5 seconds tested to BS EN/EN/IEC 61643

(2)

The maximum transient voltage let-through of the protector

throughout the test, phase to earth and neutral to earth

(3)

The electrical system, external to the unit, may constrain the

actual current rating achieved in a particular installation

(4)

The remote signal contact (removable) adds 10 mm to height