Total Solution to Earthing & Lightning Protection |
9AKK106354A3360
11
Mains power protection
ESP M2/M4 Series
Combined Type 1, 2 and 3 tested protector (to BS EN 61643) for use on the main
distribution board directly feeding electronic equipment such as computers,
communication and control equipment, particularly where a structural Lightning
Protection System (LPS) is employed. For use at boundaries up to LPZ
0
to
protect against flashover (typically the main distribution board location) through
to LPZ 3 to protect sensitive electronic equipment.
Installation
Install in parallel, within the power distribution board, either on
the load side of the incoming isolator, or on the closest outgoing
way to the incoming supply. Connect, with very short
connecting leads, to phase(s), neutral and earth. Phase/live
connecting leads should be fused with HRC fuses, a switchfuse,
MCCB or type ‘C’ MCB. For TT installations, contact Furse.
Accessories
Weatherproof enclosures:
WBX M2
For use with the ESP XXX M2
WBX M4
For use with the ESP XXX M4
Full product range order codes can be found on pages 17/8-17/9
NOTE:
For main distribution boards with multiple metallic services (gas, water, telecom/data lines) entering and for sub-distribution boards, the ESP M1 Series
are more suited. If your supply is fused at 16 Amps, or less, the in-line protection (ESP 240 or 120-5A (or -16A) and ready-boxed derivatives) may be suitable.
If you need to mount the display panel separately from the main protector unit, use the ESP XXX M2R or ESP XXX M4R.
Parallel connection to three phase star (4 wire
and earth) supplies (fuses not shown for clarity)
DIRTY
CLEAN
To
load
From
supply
Application
Use ESP M2 versions on main distribution board for buildings
with a Class III or IV structural LPS fitted or exposed 3 phase
power lines where no LPS is fitted. Use ESP M4 versions
on main distribution board for buildings with a Class I or II
LPS fitted.
Features & benefits
–– Very low let-through voltage (enhanced protection to
IEC/BS EN 62305) between all sets of conductors (phase
to neutral, phase to earth and neutral to earth - Full Mode
protection)
–– Full Mode design capable of handling high energy partial
lightning currents as well as allowing continual operation of
protected equipment
–– Innovative multiple thermal disconnect technology, for safe
disconnection from faulty or abnormal supplies (without
compromising protective performance)
–– Three way visual indication of protection status
–– Advanced pre-failure warning so you need never be
unprotected
–– Remote indication facility allows pre-failure warning to be
linked to a building management system, buzzer or light
–– Changeover active volt-free contact enables the protector
to be used to warn of phase loss (i.e. power failure,
blown fuses, etc)
–– Unique flashing warning of potentially fatal neutral to earth
supply faults (caused by incorrect earthing, wiring errors
or unbalanced conditions)
–– Robust steel housing
–– Protector base provides ultra low inductance earth bond
to metal panels
–– Convenient holes for flat mounting