ESP M1R, M2R & M4R Series - Technical specification
Electrical specification
ESP 415 M1R
ESP 480 M1R
ESP 415 M2R
ESP 480 M2R
ESP 415 M4R
ESP 480 M4R
ABB order code
7TCA085460R0115 7TCA085460R0137 7TCA085460R0123 7TCA085460R0078 7TCA085460R0126 7TCA085460R0340
Nominal voltage - Phase-Neutral
U
o (RMS)
240 V
277 V
240 V
277 V
240 V
277 V
Maximum voltage - Phase-Neutral
U
c (RMS)
280 V
350 V
280 V
350 V
280 V
350 V
Temporary Overvoltage TOV
U
T
(1)
350 V
402 V
350 V
402 V
350 V
402 V
Short circuit withstand capability
25 kA/50 Hz
Working voltage (RMS)
346-484 V
402-600 V
346-484 V
402-600 V
346-484 V
402-600 V
Frequency range
47-63 Hz
Max. back-up fuse (see installation instructions)
≤ 125 A
≤ 125 A
≤ 200 A
≤ 200 A
≤ 315 A
≤ 315 A
Leakage current (to earth)
< 250 μA
< 250 μA
< 500 μA
<500 μA
< 1000 μA
< 1000 μA
Indicator circuit current
< 10 mA
< 10 mA
< 20 mA
< 20 mA
< 40 mA
< 40 mA
Volt free contact:
(2)
Screw terminal
– Current rating
1 A
– Nominal voltage (RMS)
250 V
Transient specification
ESP 415 M1R
ESP 480 M1R
ESP 415 M2R
ESP 480 M2R
ESP 415 M4R
ESP 480 M4R
Type 1 (BS EN/EN), Class I (IEC)
Nominal discharge current 8/20 μs (per mode)
I
n
20 kA
20 kA
20 kA
20 kA
25 kA
25 kA
Let-through voltage
U
p at
I
n
< 1.3 kV
< 1.4 kV
< 1.3 kV
< 1.4 kV
< 1.4 kV
< 1.5 kV
Impulse discharge current 10/350 μs
I
imp (to earth)
(4)
4 kA
4 kA
12.5 kA
12.5 kA
25 kA
25 kA
Let-through voltage Up at
I
imp
(3)
750 V
850 V
< 1.2 kV
< 1.4 kV
< 1.3 kV
< 1.5 kV
Total discharge current 10/350 µs
I
total (total to earth)
(4,5)
16 kA
16 kA
50 kA
50 kA
100 kA
100 kA
Type 2 (BS EN/EN), Class II (IEC)
Nominal discharge current 8/20 μs (per mode)
I
n
20 kA
20 kA
20 kA
20 kA
25 kA
25 kA
Let-through voltage
U
p at
I
n
(3)
< 1.3 kV
< 1.4 kV
< 1.3 kV
< 1.4 kV
< 1.4 kV
< 1.5 kV
Maximum discharge current
I
max (L/N-PE, L-N)
(4)
40 kA, 40 kA
40 kA, 40 kA
80 kA, 40 kA
80 kA, 40 kA
150 kA, 40 kA
150 kA, 40 kA
Type 3 (BS EN/EN), Class III (IEC)
Let-through voltage at
U
oc of 6 kV 1.2/50 μs and
Is
c of 3 kA 8/20 μs (per mode)
(3,6)
600 V
680 V
600 V
680 V
600 V
680 V
Mechanical specification
ESP 415 M1R
ESP 480 M1R
ESP 415 M2R
ESP 480 M2R
ESP 415 M4R
ESP 480 M4R
Temperature range
-40 to +80 °C
Connection type
Screw terminal - maximum torque 1.5 Nm (ESP M1R), 2.5 Nm (ESP M2R), 5.6 Nm (ESP M4R)
Conductor size (stranded)
16 mm
2
16 mm
2
25 mm
2
25 mm
2
50 mm
2
50 mm
2
Earth connection
Screw terminal - maximum torque 1.5 Nm (ESP M1R), 2.5 Nm (ESP M2R), 5.6 Nm (ESP M4R)
Volt free contact
Connect via screw terminal with conductor up to 2.5 mm
2
(stranded) - maximum torque 0.25 Nm
Degree of protection (IEC 60529)
IP20
Display connection
6 way 1 metre interconnection cable - 2 or 4 metre cable optional
Case material
Unit - Steel, Display - FR Polymer UL-94 V0
Weight: – Unit
1.0 kg
1.0 kg
2.35 kg
2.35 kg
3.9 kg
3.9 kg
– Packaged
1.1 kg
1.1 kg
2.5 kg
2.5 kg
4.2 kg
4.2 kg
Dimensions
See diagrams below
(1)
Temporary Overvoltage rating is for a maximum duration of
5 seconds tested to BS EN/EN/IEC 61643
(2)
Minimum permissable load is 5 V DC, 10 mA to ensure reliable
operation. Under fault conditions, the remote display will go
blank if the L1 phase loses power or becomes faulty.
This is due to the isolation requirements needed for circuitry
mounted externally to the main protector unit
(3)
The maximum transient voltage let-through of the protector
throughout the test (±10%), phase to neutral, phase to
earth and neutral to earth
(4)
The electrical system, external to the unit, may constrain the
actual current rating achieved in a particular installation
(5)
Rating is considered as the current capability of the protector
for equipotential bonding near the service entrance
(6)
Combination wave test within IEC/BS EN 61643,
IEEE C62.41-2002 Location Cats C1 & B3, SS 555:2010,
AS/NZS 1768-2007, UL 1449 mains wire-in
ESP XXX M1R
110 mm
90 mm
165 mm
35.5 mm
70 mm
70.5 mm
Ø 15 mm
ESP XXX M2R/M4R
M5 Clearance
Note: The unit takes
up 20 mm (ESP M1),
or 25 mm (ESP M2/M4)
of the length of the
fixing screw
Display unit (rear view)
M3 threaded
Depth: 12 mm
(60 mm depth required
behind panel for plug)
Depth:
73 mm (ESP M1R)
78 mm (ESP M2R)
125 mm (ESP M4R)
226 mm
176 mm
204 mm
180 mm
55 mm
186.5 mm
Mains power protection
ESP M1R, M2R & M4R Series