ESP M1R, M2R & M4R Series - Technical specification

Electrical specification

ESP 415 M1R

ESP 480 M1R

ESP 415 M2R

ESP 480 M2R

ESP 415 M4R

ESP 480 M4R

ABB order code

7TCA085460R0115 7TCA085460R0137 7TCA085460R0123 7TCA085460R0078 7TCA085460R0126 7TCA085460R0340

Nominal voltage - Phase-Neutral

U

o (RMS)

240 V

277 V

240 V

277 V

240 V

277 V

Maximum voltage - Phase-Neutral

U

c (RMS)

280 V

350 V

280 V

350 V

280 V

350 V

Temporary Overvoltage TOV

U

T

(1)

350 V

402 V

350 V

402 V

350 V

402 V

Short circuit withstand capability

25 kA/50 Hz

Working voltage (RMS)

346-484 V

402-600 V

346-484 V

402-600 V

346-484 V

402-600 V

Frequency range

47-63 Hz

Max. back-up fuse (see installation instructions)

≤ 125 A

≤ 125 A

≤ 200 A

≤ 200 A

≤ 315 A

≤ 315 A

Leakage current (to earth)

< 250 μA

< 250 μA

< 500 μA

<500 μA

< 1000 μA

< 1000 μA

Indicator circuit current

< 10 mA

< 10 mA

< 20 mA

< 20 mA

< 40 mA

< 40 mA

Volt free contact:

(2)

Screw terminal

– Current rating

1 A

– Nominal voltage (RMS)

250 V

Transient specification

ESP 415 M1R

ESP 480 M1R

ESP 415 M2R

ESP 480 M2R

ESP 415 M4R

ESP 480 M4R

Type 1 (BS EN/EN), Class I (IEC)

Nominal discharge current 8/20 μs (per mode)

I

n

20 kA

20 kA

20 kA

20 kA

25 kA

25 kA

Let-through voltage

U

p at

I

n

< 1.3 kV

< 1.4 kV

< 1.3 kV

< 1.4 kV

< 1.4 kV

< 1.5 kV

Impulse discharge current 10/350 μs

I

imp (to earth)

(4)

4 kA

4 kA

12.5 kA

12.5 kA

25 kA

25 kA

Let-through voltage Up at

I

imp

(3)

750 V

850 V

< 1.2 kV

< 1.4 kV

< 1.3 kV

< 1.5 kV

Total discharge current 10/350 µs

I

total (total to earth)

(4,5)

16 kA

16 kA

50 kA

50 kA

100 kA

100 kA

Type 2 (BS EN/EN), Class II (IEC)

Nominal discharge current 8/20 μs (per mode)

I

n

20 kA

20 kA

20 kA

20 kA

25 kA

25 kA

Let-through voltage

U

p at

I

n

(3)

< 1.3 kV

< 1.4 kV

< 1.3 kV

< 1.4 kV

< 1.4 kV

< 1.5 kV

Maximum discharge current

I

max (L/N-PE, L-N)

(4)

40 kA, 40 kA

40 kA, 40 kA

80 kA, 40 kA

80 kA, 40 kA

150 kA, 40 kA

150 kA, 40 kA

Type 3 (BS EN/EN), Class III (IEC)

Let-through voltage at

U

oc of 6 kV 1.2/50 μs and

Is

c of 3 kA 8/20 μs (per mode)

(3,6)

600 V

680 V

600 V

680 V

600 V

680 V

Mechanical specification

ESP 415 M1R

ESP 480 M1R

ESP 415 M2R

ESP 480 M2R

ESP 415 M4R

ESP 480 M4R

Temperature range

-40 to +80 °C

Connection type

Screw terminal - maximum torque 1.5 Nm (ESP M1R), 2.5 Nm (ESP M2R), 5.6 Nm (ESP M4R)

Conductor size (stranded)

16 mm

2

16 mm

2

25 mm

2

25 mm

2

50 mm

2

50 mm

2

Earth connection

Screw terminal - maximum torque 1.5 Nm (ESP M1R), 2.5 Nm (ESP M2R), 5.6 Nm (ESP M4R)

Volt free contact

Connect via screw terminal with conductor up to 2.5 mm

2

(stranded) - maximum torque 0.25 Nm

Degree of protection (IEC 60529)

IP20

Display connection

6 way 1 metre interconnection cable - 2 or 4 metre cable optional

Case material

Unit - Steel, Display - FR Polymer UL-94 V0

Weight: – Unit

1.0 kg

1.0 kg

2.35 kg

2.35 kg

3.9 kg

3.9 kg

– Packaged

1.1 kg

1.1 kg

2.5 kg

2.5 kg

4.2 kg

4.2 kg

Dimensions

See diagrams below

(1)

Temporary Overvoltage rating is for a maximum duration of

5 seconds tested to BS EN/EN/IEC 61643

(2)

Minimum permissable load is 5 V DC, 10 mA to ensure reliable

operation. Under fault conditions, the remote display will go

blank if the L1 phase loses power or becomes faulty.

This is due to the isolation requirements needed for circuitry

mounted externally to the main protector unit

(3)

The maximum transient voltage let-through of the protector

throughout the test (±10%), phase to neutral, phase to

earth and neutral to earth

(4)

The electrical system, external to the unit, may constrain the

actual current rating achieved in a particular installation

(5)

Rating is considered as the current capability of the protector

for equipotential bonding near the service entrance

(6)

Combination wave test within IEC/BS EN 61643,

IEEE C62.41-2002 Location Cats C1 & B3, SS 555:2010,

AS/NZS 1768-2007, UL 1449 mains wire-in

ESP XXX M1R

110 mm

90 mm

165 mm

35.5 mm

70 mm

70.5 mm

Ø 15 mm

ESP XXX M2R/M4R

M5 Clearance

Note: The unit takes

up 20 mm (ESP M1),

or 25 mm (ESP M2/M4)

of the length of the

fixing screw

Display unit (rear view)

M3 threaded

Depth: 12 mm

(60 mm depth required

behind panel for plug)

Depth:

73 mm (ESP M1R)

78 mm (ESP M2R)

125 mm (ESP M4R)

226 mm

176 mm

204 mm

180 mm

55 mm

186.5 mm

Mains power protection