11/22

Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

11

Mains power protection

ESP 5A/BX & 16A/BX Series

Combined Type 2 and 3 tested protector (to BS EN 61643) for use on low

current (up to 5 or 16 A) single phase systems to protect connected electronic

equipment from transient overvoltages on the mains supply, e.g. fire/intruder

alarm panels. Protectors with /BX suffix come ready-boxed, to IP66, for use in

dirty or damp environments. Available for 90-150 Volts, 200-280 Volts and

232-350 Volts supplies. For use at boundaries LPZ 1 through to LPZ 3 to protect

sensitive electronic equipment.

Accessories

If several

ESP 120-5A

or 16A,

ESP

240-5A

or 16A or

ESP 277-5A

or 16A

protectors are to be installed together,

or if one is in use alongside Lightning

Barriers for video or signal lines, these

can be simultaneously mounted and

earthed on a CME kit and housed in a

suitable WBX enclosure.

Full product range order codes can

be found on pages 17/8-17/9

NOTE:

If your supply is fused at more than 16 Amps the ESP 120 M1, ESP 240 M1 or ESP 277 M1 are suitable.

Connect in-line on supplies fused up to 5 A

(ESP 120-5A/BX, ESP 240-5A/BX or ESP 277-5A/BX)

or 16 A (ESP 120-16A/BX, ESP 240-16A/BX

or ESP 277-16A/BX). Note how the protector can

also be earthed from its earth stud

Connect in-line on supplies fused up to 5 A

(ESP 120-5A, ESP 240-5A or ESP 277-5A)

or 16 A (ESP 120-16A, ESP 240-16A or ESP

277-16A). Note how the protector can also

be earthed from its earth stud

47-63Hz

DIRTY

CLEAN

To

equipment

From line

DIRTY

CLEAN

To

equipment

From

line

Earth

Earth

Features & benefits

–– Very low let-through voltage (enhanced protection to

IEC/BS EN 62305) between all sets of conductors (phase

to neutral, phase to earth, neutral to earth - Full Mode

protection)

allowing continuous operation of equipment

–– Repeated protection in lightning intense environments

–– Compact size for easy incorporation in the protected

system

–– Removable DIN rail foot for simple clip-on mounting to top

hat DIN rails (unboxed versions)

–– Colour coded terminals give a quick and easy installation

check - grey for the dirty (line) end and green for the clean

end

–– Available ready-boxed to IP66 for use in dirty or damp

environments (protectors with /BX suffix)

–– Robust housing and substantial earth stud fixing holes

ready for flat mounting

–– Maintenance free

–– ESP 240-5A/BX has Network Rail Approval PA05/02896.

NRS PADS reference 087/037285

Installation

Connect in-line with the power supply usually either within the

equipment panel (or for CCTV cameras, in an enclosure close

by), or on the fused connection that supplies equipment.

To protect equipment inside a building from transients

entering on an outgoing feed (e.g. to CCTV cameras or to

site lighting) the protector should be installed as close to

where the cable leaves the building as possible.

Unless ready boxed, protectors should be installed either

within an existing cabinet/cubicle or in a separate enclosure.

Application

Use these protectors on low current mains power supplies,

e.g. CCTV cameras, alarm panels and telemetry equipment.