ESP D1 Series (Three phase) - Technical specification

Electrical specification

ESP 208 D1

(1)

ESP 415 D1

(1)

ESP 480 D1

(1)

ABB order code

7TCA085460R0077 7TCA085460R0105 7TCA085460R0133

Nominal voltage - Phase-Neutral

U

o (RMS)

120 V

240 V

277 V

Maximum voltage - Phase-Neutral

U

c (RMS)

150 V

280 V

350 V

Temporary Overvoltage TOV

U

T

(2)

175 V

350 V

402 V

Short circuit withstand capability

25 kA/50 Hz

Working voltage (RMS)

90-150 V

200-280 V

232-350 V

Frequency range

47-63 Hz

Max. back-up fuse (see installation instructions)

≤ 125 A

Leakage current (to earth)

< 250 μA

Indicator circuit current

< 10 mA

Volt free contact:

(3)

Screw terminal

– Current rating

1 A

– Nominal voltage (RMS)

250 V

Transient specification

ESP 208 D1

ESP 415 D1

ESP 480 D1

Type 1 (BS EN/EN), Class I (IEC)

Nominal discharge current 8/20 μs (per mode)

I

n

20 kA

Let-through voltage

U

p at

I

n

< 1 kV

< 1.3 kV

< 1.4 kV

Impulse discharge current 10/350 μs

I

imp (to earth)

(5)

4 kA

Let-through voltage

U

p at

I

imp

< 1 kV

< 1.2 kV

< 1.3 kV

Total discharge current 10/350 μs

I

total (total to earth)

(5,6)

16 kA

16 kA

16 kA

Type 2 (BS EN/EN), Class II (IEC)

Nominal discharge current 8/20 μs (per mode)

I

n

20 kA

Let-through voltage

U

p at

I

n

< 1 kV

< 1.3 kV

< 1.4 kV

Maximum discharge current

I

max (L/N-E, L-N)

(5)

40 kA, 40 kA

Type 3 (BS EN/EN), Class III (IEC)

Let-through voltage at

U

oc of 6 kV 1.2/50 μs and

Is

c of 3 kA 8/20 μs (per mode)

(4,7)

400 V

600 V

680 V

Mechanical specification

ESP 120 D1

ESP 240 D1

ESP 277 D1

Temperature range

-40 to +80 °C

Connection type

Screw terminal - maximum torque 4.5Nm

Conductor size (stranded)

25 mm

2

Earth connection

Screw terminal - maximum torque 4.5Nm

Volt free contact

Connect via screw terminal with conductor up to 1.5 mm

2

(stranded) - maximum torque 0.25 Nm

Display connection (D1R & D1R/LCD versions)

HD-D Type 1 metre interconnection cable / 2 metre cable (ESP RLA HD-2) or 4 metre cable (ESP RLA HD-4) optional

Degree of protection (IEC 60529)

IP20

Case material

FR Polymer UL-94 V-0

Weight: – Unit

0.85 kg

– Packaged

0.95 kg

Dimensions to DIN 43880 - HxDxW

(8)

90 mm x 88 mm x 144 mm (8TE)

(1)

Three phase series (208 V, 415 V or 480 V) include fixed (D1)

or remote (D1R) LED or LCD options, e.g. ESP 415 D1,

ESP 415 D1/LCD, ESP 415 D1R, ESP 415 D1R/LCD

(2)

Temporary Overvoltage rating is for a maximum duration of

5 seconds tested to IEC/BS EN 61463

(3)

Min. permissable load is 5 V DC, 10 mA to ensure reliable operation

(4)

The maximum transient voltage let-through of the protector

throughout the test (±10%), phase to neutral, phase to

earth and neutral to earth

(5)

The electrical system, external to the unit, may constrain the

actual current rating achieved in a particular installation

(6)

Rating is considered as the current capability of the protector

for equipotential bonding near the service entrance

(7)

Combination wave test within IEC/BS EN 61643,

IEEE C62.41-2002 Location Cats C1 & B3, SS 555:2010,

AS/NZS 1768-2007, UL 1449 mains wire-in

(8)

The remote signal contact (removable) adds 10 mm to height

90 mm

36 mm

72 mm

DIN 72x36 cutout (68 x 33 mm)

Depth 20 mm

(60 mm depth required

behind panel for plug)

Display Unit

144 mm

50 mm 38 mm

Standard

depth

88 mm

Mains power protection