Table of Contents Table of Contents
Previous Page  231 / 336 Next Page
Information
Show Menu
Previous Page 231 / 336 Next Page
Page Background

Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

12/5

12

ESP D & TN Series - Technical specification

Electrical specification

ESP 06D

ESP 15D

ESP 30D

ESP 50D

ESP 110D

ESP TN

ABB order code

7TCA085400R0079 7TCA085400R0089 7TCA085400R0099 7TCA085400R0109 7TCA085400R0005 7TCA085400R0171

Nominal voltage

(1)

6 V

15 V

30 V

50 V

110 V

Maximum working voltage

U

c (RMS/DC)

(2)

5 V / 7.79 V

13 V / 19 V

26 V / 37.1 V

41 V / 58 V

93 V / 132 V

– / 296 V

Current rating (signal)

300 mA

In-line resistance (per line ±10%)

9.4 Ω

9.4 Ω

9.4 Ω

9.4 Ω

9.4 Ω

4.4 Ω

Bandwidth (-3 dB 50 Ω system)

800 kHz

2.5 MHz

4 MHz

6 MHz

9 MHz

20 MHz

Transient specification

ESP 06D

ESP 15D

ESP 30D

ESP 50D

ESP 110D

ESP TN

Let-through voltage (all conductors)

(3)

U

p

C2 test 4 kV 1.2/50 μs, 2 kA 8/20 μs to

BS EN/EN/IEC 61643-21

12.0 V

25.0 V

44.0 V

78.0 V

155 V

395 V

C1 test 1 kV, 1.2/50 μs, 0.5 kA 8/20 μs to

BS EN/EN/IEC 61643-21

11.5 V

24.5 V

43.5 V

76.0 V

150 V

390 V

B2 test 4 kV 10/700 μs to BS EN/EN/IEC 61643-21

10.0 V

23.0 V

42.5 V

73.0 V

145 V

298 V

5 kV, 10/700 μs

(4)

10.5 V

23.8 V

43.4 V

74.9 V

150 V

300 V

Maximum surge current

D1 test 10/350 μs to – Per signal wire

2.5 kA

BS EN/EN/IEC 61643-21: – Per pair

5 kA

8/20 μs to ITU-T K.45:2003, – Per signal wire

10 kA

IEEE C62.41.2:2002: – Per pair

20 kA

Mechanical specification

ESP 06D

ESP 15D

ESP 30D

ESP 50D

ESP 110D

ESP TN

Temperature range

-40 to +80 °C

Connection type

Screw terminal - maximum torque 0.5 Nm

Conductor size (stranded)

2.5 mm

2

Earth connection

M6 stud

Case material

FR Polymer UL-94 V-0

Weight: – Unit

0.08 kg

– Packaged (per 10)

0.85 kg

Dimensions

See diagram below

(1)

Nominal voltage (RMS/DC or AC peak) measured at < 5 μA

(ESP 15D, ESP 30D, ESP 50D, ESP 110D) and <200 μA (ESP 06D)

(2)

Maximum working voltage (RMS/DC or AC peak) measured at

< 1 mA leakage (ESP 15D, ESP 30D, ESP 50D, ESP 110D),

< 10 mA (ESP 06D) and < 10 μA (ESP TN)

(3)

The maximum transient voltage let-through of the protector

throughout the test (±10%), line to line & line to earth,

both polarities. Response time < 10 ns

(4)

Test to IEC 61000-4-5:2006, ITU-T (formerly CCITT) K.20,

K.21 and K.45,Telcordia GR-1089-CORE, Issue 2:2002,

ANSI TIA/EIA/IS-968-A:2002 (formerly FCC Part 68)

120 mm

38 mm

19 mm

54 mm

105 mm

M4 clearance

109 mm

M4 clearance

Data & signal protection

ESP D & TN Series