Table of Contents Table of Contents
Previous Page  234 / 336 Next Page
Information
Show Menu
Previous Page 234 / 336 Next Page
Page Background

12/8

Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

12

Combined Category D, C, B tested protector (to BS EN 61643) suitable

for twisted pair signalling applications which require either a lower in-line

resistance or an increased current than the ESP D or E Series. Also suitable

for DC power applications less than 4 Amps. Available for working voltages

of up to 6, 15, 30, 50 and 110 Volts. For use at boundaries up to LPZ

0

to

protect against flashover (typically the service entrance location) through to

LPZ 3 to protect sensitive electronic equipment.

Data & signal protection

ESP H Series

Installation

Connect in series with the data communication or signal line

either near where it enters or leaves the building or close to

the equipment being protected (e.g. within its control panel).

Either way, it must be very close to the system’s earth star

point. Install protectors either within an existing cabinet/

cubicle or in a separate enclosure.

Accessories

Combined Mounting/Earthing kits:

CME 4

Mount & earth up to 4 protectors

CME 8

Mount & earth up to 8 protectors

CME 16

Mount & earth up to 16 protectors

CME 32

Mount & earth up to 32 protectors

Weatherproof enclosures:

WBX 2/G

For use with up to 2 protectors

WBX 3, WBX 3/G

For use with up to 3 protectors

WBX 4, WBX 4/GS

For use with a CME 4 and up to 4

protectors

WBX 8, WBX 8/GS

For use with a CME 8 and up to 8

protectors

WBX 16/2/G

For use with one or two CME 16 and up to

32 protectors

Full product range order codes can

be found on pages 17/8-17/9

Install in series (in-line)

DIRTY

CLEAN

From line To equipment

Earth

Features & benefits

–– Very low let-through voltage (enhanced protection to

IEC/BS EN 62305) between all lines - Full Mode protection

–– Full Mode design capable of handling partial lightning

currents as well as allowing continual operation of

protected equipment

–– Repeated protection in lightning intense environments

–– Ultra-low (< 0.05 Ω) in-line resistance allows resistance

critical applications (e.g. alarm loops) to be protected

–– Very high (4 A) maximum running current

–– Strong, flame retardant ABS housing

–– Supplied ready for flat mounting on base or side

–– Built-in DIN rail foot for simple clip-on mounting to top

hat DIN rails

–– Colour coded terminals give a quick and easy installation

check - grey for the dirty (line) end and green for clean

–– Screen terminal enables easy connection of cable screen

to earth

–– Substantial earth stud to enable effective earthing

–– Integral earth plate enables enhanced connection to

earth via CME kit

Application

Use these applications to protect resistance sensitive or

higher running current systems, e.g. systems with long signal

lines, or DC power applications.

NOTE:

For some data and signal applications with lower current, higher in-line resistance or higher bandwidth requirements, the ESP D or E Series protectors

or the Slim Line ESP SL Series may be more suitable. If the protector is to be mounted directly onto a PCB, use the ESP PCB/**D or ESP PCB/**E protectors.