Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

12/9

12

ESP H Series - Technical specification

Electrical specification

ESP 06H

ESP 15H

ESP 30H

ESP 50H

ESP 110H

ABB order code

7TCA085400R0003 7TCA085400R0009 7TCA085400R0011 7TCA085400R0012 7TCA085400R0008

Nominal voltage

(1)

6 V

15 V

30 V

50 V

110 V

Maximum working voltage

U

c (RMS/DC)

(2)

5 V / 7.79 V

11 V / 16.7 V

25 V / 36.7 V

40 V / 56.7 V

93 V / 132 V

Current rating (signal)

4 A

In-line resistance (per line ±10%)

0.05 Ω

Bandwidth (-3 dB 50 Ω system)

160 KHz

140 KHz

130 KHz

120 KHz

120 KHz

Transient specification

ESP 06H

ESP 15H

ESP 30H

ESP 50H

ESP 110H

Let-through voltage (all conductors)

(3)

U

p

C2 test 4 kV 1.2/50 μs, 2 kA 8/20 μs to

BS EN/EN/IEC 61643-21

12.0 V

27.5 V

46.0 V

67.0 V

150 V

C1 test 1 kV, 1.2/50 μs, 0.5 kA 8/20 μs to

BS EN/EN/IEC 61643-21

11.0 V

26.5 V

45.0 V

66.5 V

145 V

B2 test 4 kV 10/700 μs to BS EN/EN/IEC 61643-21

10.5 V

25.5 V

43.5 V

65.0 V

140 V

5 kV, 10/700 μs

(4)

10.8 V

26.2 V

44.3 V

65.8 V

145 V

Maximum surge current

D1 test 10/350 μs to – Per signal wire

2.5 kA

BS EN/EN/IEC 61643-21: – Per pair

5 kA

8/20 μs to ITU-T K.45:2003, – Per signal wire

10 kA

IEEE C62.41.2:2002: – Per pair

20 kA

Mechanical specification

ESP 06E

ESP 15E

ESP 30E

ESP 50E

ESP 110E

Temperature range

-40 to +80 °C

Connection type

Screw terminal - maximum torque 0.5 Nm

Conductor size (stranded)

2.5 mm

2

Earth connection

M6 stud - maximum torque 0.5 Nm

Case material

FR Polymer UL-94 V-0

Weight: – Unit

0.08 kg

– Packaged (per 10)

0.85 kg

Dimensions

See diagram below

(1)

Nominal voltage (RMS/DC or AC peak) measured at < 10 μA

(ESP 15H, ESP 30H, ESP 50H, ESP 110H) and < 200 μA (ESP 06H)

(2)

Maximum working voltage (RMS/DC or AC peak) measured at

< 5 mA leakage (ESP 15H, ESP 30H, ESP 50H, ESP 110H) and

< 10 mA (ESP 06H)

(3)

The maximum transient voltage let-through of the protector

throughout the test (±10%), line to line & line to earth,

both polarities. Response time < 10 ns

(4)

Test to IEC 61000-4-5:2006, ITU-T (formerly CCITT) K.20,

K.21 and K.45,Telcordia GR-1089-CORE, Issue 2:2002,

ANSI TIA/EIA/IS-968-A:2002 (formerly FCC Part 68)

120 mm

38 mm

19 mm

54 mm

105 mm

M4 clearance

109 mm

M4 clearance

Data & signal protection

ESP H Series