Total Solution to Earthing & Lightning Protection |
9AKK106354A3360
12/9
12
ESP H Series - Technical specification
Electrical specification
ESP 06H
ESP 15H
ESP 30H
ESP 50H
ESP 110H
ABB order code
7TCA085400R0003 7TCA085400R0009 7TCA085400R0011 7TCA085400R0012 7TCA085400R0008
Nominal voltage
(1)
6 V
15 V
30 V
50 V
110 V
Maximum working voltage
U
c (RMS/DC)
(2)
5 V / 7.79 V
11 V / 16.7 V
25 V / 36.7 V
40 V / 56.7 V
93 V / 132 V
Current rating (signal)
4 A
In-line resistance (per line ±10%)
0.05 Ω
Bandwidth (-3 dB 50 Ω system)
160 KHz
140 KHz
130 KHz
120 KHz
120 KHz
Transient specification
ESP 06H
ESP 15H
ESP 30H
ESP 50H
ESP 110H
Let-through voltage (all conductors)
(3)
U
p
C2 test 4 kV 1.2/50 μs, 2 kA 8/20 μs to
BS EN/EN/IEC 61643-21
12.0 V
27.5 V
46.0 V
67.0 V
150 V
C1 test 1 kV, 1.2/50 μs, 0.5 kA 8/20 μs to
BS EN/EN/IEC 61643-21
11.0 V
26.5 V
45.0 V
66.5 V
145 V
B2 test 4 kV 10/700 μs to BS EN/EN/IEC 61643-21
10.5 V
25.5 V
43.5 V
65.0 V
140 V
5 kV, 10/700 μs
(4)
10.8 V
26.2 V
44.3 V
65.8 V
145 V
Maximum surge current
D1 test 10/350 μs to – Per signal wire
2.5 kA
BS EN/EN/IEC 61643-21: – Per pair
5 kA
8/20 μs to ITU-T K.45:2003, – Per signal wire
10 kA
IEEE C62.41.2:2002: – Per pair
20 kA
Mechanical specification
ESP 06E
ESP 15E
ESP 30E
ESP 50E
ESP 110E
Temperature range
-40 to +80 °C
Connection type
Screw terminal - maximum torque 0.5 Nm
Conductor size (stranded)
2.5 mm
2
Earth connection
M6 stud - maximum torque 0.5 Nm
Case material
FR Polymer UL-94 V-0
Weight: – Unit
0.08 kg
– Packaged (per 10)
0.85 kg
Dimensions
See diagram below
(1)
Nominal voltage (RMS/DC or AC peak) measured at < 10 μA
(ESP 15H, ESP 30H, ESP 50H, ESP 110H) and < 200 μA (ESP 06H)
(2)
Maximum working voltage (RMS/DC or AC peak) measured at
< 5 mA leakage (ESP 15H, ESP 30H, ESP 50H, ESP 110H) and
< 10 mA (ESP 06H)
(3)
The maximum transient voltage let-through of the protector
throughout the test (±10%), line to line & line to earth,
both polarities. Response time < 10 ns
(4)
Test to IEC 61000-4-5:2006, ITU-T (formerly CCITT) K.20,
K.21 and K.45,Telcordia GR-1089-CORE, Issue 2:2002,
ANSI TIA/EIA/IS-968-A:2002 (formerly FCC Part 68)
120 mm
38 mm
19 mm
54 mm
105 mm
M4 clearance
109 mm
M4 clearance
Data & signal protection
ESP H Series