Table of Contents Table of Contents
Previous Page  241 / 336 Next Page
Information
Show Menu
Previous Page 241 / 336 Next Page
Page Background

Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

12/15

12

ESP SL X Series - Technical specification

Electrical specification

ESP SL15X

ESP SL30X

ABB order code

7TCA085400R0065 7TCA085400R0071

Nominal voltage

(1)

15 V

30 V

Maximum working voltage

U

c (RMS/DC)

(2)

11 V / 16.7 V

25 V / 36.7 V

Current rating (signal)

750 mA

In-line resistance (per line ±10%)

1.0 Ω

Bandwidth (-3 dB 50 Ω system)

45 MHz

Intrinsically safe specification

ESP SL15X

ESP SL30X

Maximum voltage

U

i

30 V

Maximum power

P

i

: – Per -40 ºC < Ta < 40 ºC

1.3 W

– Per -40 ºC < Ta < 60 ºC

1.2 W

– Per -40 ºC < Ta < 80 ºC

1.0 W

Capacitance

C

i

0 μF

Inductance

L

i

0 μH

Certificate number

IECEx SIR 10.0030X, Sira 10ATEX2063X

Classification

Ex

II 2 (1) G, Ex ia (ia Ga) IIC T4 Gb

Transient specification

ESP SL15X

ESP SL30X

Let-through voltage (all conductors)

(3)

U

p

C2 test 4 kV 1.2/50 μs, 2 kA 8/20 μs to

BS EN/EN/IEC 61643-21

38.4 V

63.0 V

C1 test 1 kV, 1.2/50 μs, 0.5 kA 8/20 μs to

BS EN/EN/IEC 61643-21

29.4 V

51.3 V

B2 test 4 kV 10/700 μs to BS EN/EN/IEC 61643-21

26.8 V

45.4 V

5 kV, 10/700 μs

(4)

27.5 V

46.3 V

Maximum surge current

D1 test 10/350 μs to – Per signal wire

1.25 kA

BS EN/EN/IEC 61643-21: – Per pair

2.5 kA

8/20 μs to ITU-T K.45:2003, – Per signal wire

10 kA

IEEE C62.41.2:2002: – Per pair

20 kA

Mechanical specification

ESP SL15X

ESP SL30X

Temperature range

-40 to +80 °C

Connection type

Screw terminal - maximum torque 0.8 Nm

Conductor size (stranded)

4 mm

2

Earth connection

Via DIN rail or 4 mm

2

earth terminal - maximum torque 0.8 Nm

Case material

FR Polymer UL-94 V-0

Weight: – Unit

0.08 kg

– Packaged (per 10)

0.85 kg

Dimensions

See diagram below

(1)

Nominal voltage (RMS/DC or AC peak) measured at < 10 μA

(2)

Maximum working voltage (RMS/DC or AC peak) measured at

< 1 mA leakage

(3)

The maximum transient voltage let-through of the protector

throughout the test (±10%), line to line & line to earth,

both polarities. Response time < 10 ns

(4)

Test to IEC 61000-4-5:2006, ITU-T (formerly CCITT) K.20,

K.21 and K.45, Telcordia GR-1089-CORE, Issue 2:2002,

ANSI TIA/EIA/IS-968-A:2002 (formerly FCC Part 68)

7 mm

104.6 mm

106.5 mm

2 S 1

2 S

E

1

Data & signal protection

ESP SL X Series