Combined Category D, C, B tested protector (to BS EN 61643) suitable for

3-wire signalling applications which require either a lower in-line resistance,

an increased current and/or higher bandwidth. Also suitable for DC power

applications less than 0.5 Amps. Available for working voltages of up to 6,

15, 30, 50 and 110 Volts. For use at boundaries up to LPZ

0

to protect against

flashover (typically the service entrance location) through to LPZ 3 to protect

sensitive electronic equipment.

Data & signal protection

ESP SL 3-Wire Series

Installation

Connect in series with the data communication or signal line

either near where it enters or leaves the building or close to

the equipment being protected (e.g. within its control panel).

Either way, it must be very close to the system’s earth star

point. Install protectors either within an existing cabinet/

cubicle or in a separate enclosure.

Accessories

Replacement modules:

ESP SLXX/3W/M

Standard module replacement where XX is

voltage rating (06, 15, 30, 50 or 110)

ESP SL/3W/B

Base replacement

Full product range order codes can be found on pages 17/8-17/9

4

5

6

1

2

3

LightningBarrier

From line

LINE

CLEAN

Earth

To equipment

Furse

Wilford Road,

Nottingham,

NG21EB,UK

Clean

Line

30V

37.8V

750mA

1.0Ω

10kA

43.5V

Nominalvoltage

Maxworkingvoltage,U

c

Currentrating

In-line resistance

Max surgecurrent

Let-throughvoltage,U

p

From line

To equipment

LINE

CLEAN

Earth

Features & benefits

–– Very low let-through voltage (enhanced protection to

IEC/BS EN 62305) between all lines - Full Mode protection

–– Full Mode design capable of handling partial lightning

currents as well as allowing continual operation of

protected equipment

–– Repeated protection in lightning intense environments

–– Ultra slim 7 mm width ideal for compact protection of large

numbers of lines (e.g. process control installations)

–– Two stage removable protection module with simple quick

release mechanism allowing partial removal for easy line

commissioning and maintenance as well as full removal for

protection replacement

–– Very low (1 Ω) in-line resistance allows resistance critical

applications (e.g. alarm loops) to be protected

–– High (500 mA) maximum running current

–– High bandwidth enables higher frequency (high traffic or

bit rate) data communications

–– Strong, flame retardant, polycarbonate housing

–– Built-in innovative DIN rail foot with locking feature for

simple positioning and clip-on mounting to top hat DIN rails

–– 4 mm

2

terminals allow for larger cross section wiring,

stranded wires terminated with ferrules or fitting two wires

into a single terminal

–– Convenient earthing through DIN foot and/or earth terminal

Application

Use these protectors for 3-wire systems where installation

space is at a premium and large numbers of lines require

protection (e.g. process control, high speed digital

communication equipment or systems with long signal lines).

NOTE:

The ESP SL ‘Slim Line’ Series is also available for protection of 2-wire systems up to 110 V, RS 485, RTD and telecommunication applications

(ESP SL Series, ESP SL RS485, ESP SL RTD and ESP SL TN). The ESP SL X Series has approvals for use in hazardous areas.