Combined Category D, C, B tested protector (to BS EN 61643) suitable for use
on ten line LSA-PLUS disconnection modules to protect individual twisted
pair data or signal lines. For use at boundaries up to LPZ
0
to protect against
flashover (typically the service entrance location) through to LPZ 3 to protect
sensitive electronic equipment.
Data & signal protection
ESP KS & KE Series
Installation
Install protectors on all data communication and signal
lines that enter or leave each building. All protectors must
be installed via the ESP KE10 earth bar. Identify the lines
requiring protection and clip the ESP KE10 on to the
disconnection modules’ earth points. Plug the protector
directly into each disconnection module requiring protection
(ensuring the correct orientation) for a series connection.
In the unlikely situation that the protector is damaged, it
will sacrifice itself and fail short circuit, taking the line out of
commission. In addition to indicating that the protector needs
replacing, this will also prevent subsequent transients from
damaging the equipment.
NOTE:
For PSTN and U interface ISDN lines on LSA-PLUS modules, use the ESP KT1 or ESP K10T1. For S/T interface ISDN lines on LSA-PLUS modules, use
the ESP KT2 or ESP K10T2. For individual twisted pair data or signal lines, use the ESP D, E or H Series Lightning Barriers. The ESP SL and ESP Q Series
Lightning Barriers are suitable for high density data and signal lines.
Features & benefits
–– Low cost protection for large numbers of data and
signal lines
–– Very low let-through voltage (enhanced protection
to IEC/BS EN 62305) between all lines - Full Mode
protection
–– Full Mode design capable of handling partial lightning
currents as well as allowing continual operation of
protected equipment
–– Repeated protection in lightning intense environments
–– Quick and easy plug-in installation
–– Colour of housing distinguishes electrically different
protectors to help avoid confusion when installed with
other protectors (e.g. the ESP KT1/2) on the same
distribution frame
–– Protect only the lines you need
–– Ridged finger holds make it easy to obtain a firm grip
for installation or removal
–– Use the ESP KE10 to provide trouble free earthing for up
to ten protectors (per disconnection module)
Application
Use these units to protect signal, data, control and
instrumentation systems with LSA-PLUS
disconnection modules.
Full product range order codes can be found on pages 17/8-17/9