Table of Contents Table of Contents
Previous Page  252 / 336 Next Page
Information
Show Menu
Previous Page 252 / 336 Next Page
Page Background

12/26

Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

12

Combined Category D, C, B tested protector (to BS EN 61643) for ‘through hole’

mounting directly onto the PCB of data communication, signal or telephone

equipment which require a lower in-line resistance, an increased current or a

higher bandwidth than the PCB/**D Series. Available for working voltages of up

to 110 Volts for AC & DC power applications up to 125 Amps. For use at

boundaries up to LPZ

0

to protect against flashover (typically the service

entrance location) through to LPZ 3 to protect sensitive electronic equipment.

Data & signal protection

ESP PCB/E Series

Installation

Connect in series, soldering pins direct onto PCB. Tracks

to line and earth pins should be as wide as practical

(see Furse Application Note AN003). Dirty (line) tracks

should be routed parallel and as close together as possible.

This should also be implemented on clean tracks, however

clean tracks should never be routed close and parallel

to line tracks or dirty barrier earth connections as earth

connections as transients can be re-introduced after the

protector due to electromagnetic coupling.

The use of an earth layer or plane is highly recommended as

this reduces the electromagnetic field produced by a transient

discharging to earth considerably, and hence the chance of

the transient being picked up on clean tracks.

Full product range order codes can be found on pages 17/8-17/9

Maximum line to clean separation. Large input

tracks and pads (using top and bottom copper

layers). Earth pin is bonded to an earth layer/plane.

All dirty (line) incoming tracks are separated from the

clean output tracks, individual line and clean tracks

are routed close together. Earth pins are bonded to an

earth layer/plane.

Clean

1 3

4

2

Line

INE

CLEAN

Line

Clean

Clean

3

4

3

4

1

2

1

2

ESP PCB/**

3

4

1

2

ESP PCB/**

1 3

4

2

CLEAN

CLEAN

LINE

Features & benefits

–– Suitable for wave soldering

–– Very low let-through voltage (enhanced protection to

IEC/BS EN 62305) between all lines - Full Mode protection

–– Full Mode design capable of handling partial lightning

currents as well as allowing continual operation of

protected equipment

–– Repeated protection in lightning intense environments

–– Very low (1 Ω) in-line resistance for resistance critical

applications

–– High (1.25 A) maximum running current

–– Higher bandwidth enables higher frequency data

communications

–– 2 pin clean end and 3 pin line end to ensure correct

insertion