9AKK106354A3360

12/21

12

ESP Q & TNQ Series - Technical specification

Electrical specification

ESP 06Q

ESP 15Q

ESP 30Q

ESP 50Q

ESP 110Q

ESP TNQ

ABB order code

7TCA085400R0087 7TCA085400R0098 7TCA085400R0107 7TCA085400R0118 7TCA085400R0088 7TCA085400R0183

Nominal voltage

(1)

6 V

15 V

30 V

50 V

110 V

Maximum working voltage

U

c (RMS/DC)

(2)

5 V / 7.79 V

13 V / 18.8 V

26 V / 37.8 V

41 V / 57.8 V

93 V / 132 V

– / 296 V

Current rating (signal)

750 mA

750 mA

750 mA

750 mA

750 mA

300 mA

In-line resistance (per line ±10%)

1.0 Ω

1.0 Ω

1.0 Ω

1.0 Ω

1.0 Ω

4.3 Ω

Bandwidth (-3 dB 50 Ω system)

1 MHz

2.5 MHz

6 MHz

5 MHz

15 MHz

20 MHz

Transient specification

ESP 06Q

ESP 15Q

ESP 30Q

ESP 50Q

ESP 110Q

ESP TNQ

Let-through voltage (all conductors)

(3)

U

p

C2 test 4 kV 1.2/50 μs, 2 kA 8/20 μs to

BS EN/EN/IEC 61643-21

15.0 V

28.0 V

53.0 V

84.0 V

188 V

395 V

C1 test 1 kV, 1.2/50 μs, 0.5 kA 8/20 μs to

BS EN/EN/IEC 61643-21

12.5 V

26.5 V

48.0 V

76.0 V

175 V

390 V

B2 test 4 kV 10/700 μs to BS EN/EN/IEC 61643-21

10.0 V

23.0 V

43.5 V

64.5 V

145 V

298 V

5 kV, 10/700 μs

(4)

10.8 V

26.2 V

44.3 V

65.8 V

150 V

300 V

Maximum surge current

D1 test 10/350 μs to – Per signal wire

2.5 kA

BS EN/EN/IEC 61643-21: – Per pair

5 kA

8/20 μs to ITU-T K.45:2003, – Per signal wire

10 kA

IEEE C62.41.2:2002: – Per pair

20 kA

Mechanical specification

ESP 06Q

ESP 15Q

ESP 30Q

ESP 50Q

ESP 110Q

ESP TNQ

Temperature range

-40 to +80 °C

Connection type

Pluggable 12 way screw terminal - maximum torque 0.6 Nm

Conductor size (stranded)

2.5 mm

2

Earth connection

Via DIN rail or M5 threaded hole in base of unit

Case material

FR Polymer UL-94 V-0

Weight: – Unit

0.1 kg

– Packaged (each)

0.12 kg

– Packaged (per 10)

1.3 kg

Dimensions

See diagram below

(1)

Nominal voltage (RMS/DC or AC peak) measured at < 5 μA

(ESP 15Q, ESP 30Q, ESP 50Q, ESP 110Q) and < 200 μA (ESP 06Q)

(2)

Maximum working voltage (RMS/DC or AC peak) measured at

< 5 mA leakage (ESP 15Q, ESP 30Q, ESP 50Q, ESP 110Q) and

< 10 μA (ESP TNQ)

(3)

The maximum transient voltage let-through of the protector

throughout the test (±10%), line to line & line to earth,

both polarities. Response time < 10 ns

(4)

Test to IEC 61000-4-5:2006, ITU-T (formerly CCITT) K.20,

K.21 and K.45, Telcordia GR-1089-CORE, Issue 2:2002,

ANSI TIA/EIA/IS-968-A:2002 (formerly FCC Part 68)

95 mm

69 mm

42 mm

M3 clearance

Depth: 18 mm

87 mm

Data & signal protection

ESP Q & TNQ Series