Total Solution to Earthing & Lightning Protection |
9AKK106354A3360
12/25
12
ESP PCB/D & PCB/TN Series - Technical specification
Electrical specification
ESP PCB/06D
ESP PCB/15D
ESP PCB/30D
ESP PCB/50D
ESP PCB/110D
ESP PCB/TN
ABB order code
7TCA085400R0038 7TCA085400R0042 7TCA085400R0154 7TCA085400R0155 7TCA085400R0040 7TCA085400R0157
Nominal voltage
(1)
6 V
15 V
30 V
50 V
110 V
–
Maximum working voltage
U
c (RMS/DC)
(2)
5 V / 7.79 V
13 V / 19 V
26 V / 37.1 V
41 V / 58 V
93 V / 132 V
– / 296 V
Current rating (signal)
300 mA
In-line resistance (per line ±10%)
9.4 Ω
9.4 Ω
9.4 Ω
9.4 Ω
9.4 Ω
4.4 Ω
Bandwidth (-3 dB 50 Ω system)
800 kHz
2.5 MHz
4 MHz
6 MHz
9 MHz
20 MHz
Transient specification
ESP PCB/06D
ESP PCB/15D
ESP PCB/30D
ESP PCB/50D
ESP PCB/110D
ESP PCB/TN
Let-through voltage (all conductors)
(3)
U
p
C2 test 4 kV 1.2/50 μs, 2 kA 8/20 μs to
BS EN/EN/IEC 61643-21
12.0 V
25.0 V
44.0 V
78.0 V
155 V
395 V
C1 test 1 kV, 1.2/50 μs, 0.5 kA 8/20 μs to
BS EN/EN/IEC 61643-21
11.5 V
24.5 V
43.5 V
76.0 V
150 V
390 V
B2 test 4 kV 10/700 μs to BS EN/EN/IEC 61643-21
10.0 V
23.0 V
42.5 V
73.0 V
145 V
298 V
5 kV, 10/700 μs
(4)
10.5 V
23.8 V
43.4 V
74.9 V
150 V
300 V
Maximum surge current
(5)
D1 test 10/350 μs to – Per signal wire
2.5 kA
BS EN/EN/IEC 61643-21: – Per pair
5 kA
8/20 μs to ITU-T K.45:2003, – Per signal wire
10 kA
IEEE C62.41.2:2002: – Per pair
20 kA
Mechanical specification
ESP PCB/D & PCB/TN Series
Temperature range
-40 to +80 °C
Connection type
0.64 mm (0.025”) square PCB pins, 1.2 mm diameter PCB holes recommended
Case Material
FR Polymer UL-94 V-0
Dimensions
See diagram below
(1)
Nominal voltage (RMS/DC or AC peak) measured at < 5 μA
(ESP PCB/15D, ESP PCB/30D, ESP PCB/50D, ESP PCB/110D)
and <200 μA (ESP PCB/06D)
(2)
Maximum working voltage (RMS/DC or AC peak) measured at
< 1 mA leakage (ESP PCB/15D, ESP PCB/30D, ESP PCB/50D,
ESP PCB/110D), < 10 mA (ESP PCB/06D) and < 10 μA
(ESP PCB/TN)
(3)
The maximum transient voltage let-through of the protector
throughout the test (±10%), line to line & line to earth,
both polarities. Response time < 10 ns
(4)
Test to IEC 61000-4-5:2006, ITU-T (formerly CCITT) K.20,
K.21 and K.45,Telcordia GR-1089-CORE, Issue 2:2002,
ANSI TIA/EIA/IS-968-A:2002 (formerly FCC Part 68)
(5)
The installation and connections external to the protector
may limit the capability of the protector
30 mm
(~1 1/2”)
22.86 mm
(0.9”)
1
2
4 3
5.08 mm
(0.2”)
5.08 mm
(0.2”)
5.08 mm
(0.2”)
Depth: 20 mm (~0.8”)
Weight: 35 g
Pins are positioned centrally
Pin 1 connects through Pin 3
Pin 2 connects through Pin 4
(Underside pin view)
30 mm
(~1 1/2”)
Data & signal protection
ESP PCB/D & PCB/TN Series