Table of Contents Table of Contents
Previous Page  251 / 336 Next Page
Information
Show Menu
Previous Page 251 / 336 Next Page
Page Background

Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

12/25

12

ESP PCB/D & PCB/TN Series - Technical specification

Electrical specification

ESP PCB/06D

ESP PCB/15D

ESP PCB/30D

ESP PCB/50D

ESP PCB/110D

ESP PCB/TN

ABB order code

7TCA085400R0038 7TCA085400R0042 7TCA085400R0154 7TCA085400R0155 7TCA085400R0040 7TCA085400R0157

Nominal voltage

(1)

6 V

15 V

30 V

50 V

110 V

Maximum working voltage

U

c (RMS/DC)

(2)

5 V / 7.79 V

13 V / 19 V

26 V / 37.1 V

41 V / 58 V

93 V / 132 V

– / 296 V

Current rating (signal)

300 mA

In-line resistance (per line ±10%)

9.4 Ω

9.4 Ω

9.4 Ω

9.4 Ω

9.4 Ω

4.4 Ω

Bandwidth (-3 dB 50 Ω system)

800 kHz

2.5 MHz

4 MHz

6 MHz

9 MHz

20 MHz

Transient specification

ESP PCB/06D

ESP PCB/15D

ESP PCB/30D

ESP PCB/50D

ESP PCB/110D

ESP PCB/TN

Let-through voltage (all conductors)

(3)

U

p

C2 test 4 kV 1.2/50 μs, 2 kA 8/20 μs to

BS EN/EN/IEC 61643-21

12.0 V

25.0 V

44.0 V

78.0 V

155 V

395 V

C1 test 1 kV, 1.2/50 μs, 0.5 kA 8/20 μs to

BS EN/EN/IEC 61643-21

11.5 V

24.5 V

43.5 V

76.0 V

150 V

390 V

B2 test 4 kV 10/700 μs to BS EN/EN/IEC 61643-21

10.0 V

23.0 V

42.5 V

73.0 V

145 V

298 V

5 kV, 10/700 μs

(4)

10.5 V

23.8 V

43.4 V

74.9 V

150 V

300 V

Maximum surge current

(5)

D1 test 10/350 μs to – Per signal wire

2.5 kA

BS EN/EN/IEC 61643-21: – Per pair

5 kA

8/20 μs to ITU-T K.45:2003, – Per signal wire

10 kA

IEEE C62.41.2:2002: – Per pair

20 kA

Mechanical specification

ESP PCB/D & PCB/TN Series

Temperature range

-40 to +80 °C

Connection type

0.64 mm (0.025”) square PCB pins, 1.2 mm diameter PCB holes recommended

Case Material

FR Polymer UL-94 V-0

Dimensions

See diagram below

(1)

Nominal voltage (RMS/DC or AC peak) measured at < 5 μA

(ESP PCB/15D, ESP PCB/30D, ESP PCB/50D, ESP PCB/110D)

and <200 μA (ESP PCB/06D)

(2)

Maximum working voltage (RMS/DC or AC peak) measured at

< 1 mA leakage (ESP PCB/15D, ESP PCB/30D, ESP PCB/50D,

ESP PCB/110D), < 10 mA (ESP PCB/06D) and < 10 μA

(ESP PCB/TN)

(3)

The maximum transient voltage let-through of the protector

throughout the test (±10%), line to line & line to earth,

both polarities. Response time < 10 ns

(4)

Test to IEC 61000-4-5:2006, ITU-T (formerly CCITT) K.20,

K.21 and K.45,Telcordia GR-1089-CORE, Issue 2:2002,

ANSI TIA/EIA/IS-968-A:2002 (formerly FCC Part 68)

(5)

The installation and connections external to the protector

may limit the capability of the protector

30 mm

(~1 1/2”)

22.86 mm

(0.9”)

1

2

4 3

5.08 mm

(0.2”)

5.08 mm

(0.2”)

5.08 mm

(0.2”)

Depth: 20 mm (~0.8”)

Weight: 35 g

Pins are positioned centrally

Pin 1 connects through Pin 3

Pin 2 connects through Pin 4

(Underside pin view)

30 mm

(~1 1/2”)

Data & signal protection

ESP PCB/D & PCB/TN Series