Table of Contents Table of Contents
Previous Page  256 / 336 Next Page
Information
Show Menu
Previous Page 256 / 336 Next Page
Page Background

12/30

Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

12

LPZ

RTD

0

A

3

RTDQ

0

A

3

SL RTD

0

B

3

Data & signal protection

ESP RS485, RS485Q & SL RS485 Series

NOTE:

The ESP SL ‘Slim Line’ Series is also available for protection of 3-wire and RTD applications (ESP SL/3W & ESP SL RTD). The ESP SL X Series has

approvals for use in hazardous areas.

Combined Category D, C, B tested protector (to BS EN 61643) specifically

designed for RS 485 and Fieldbus applications, such as Profibus DP.

For use at boundaries up to LPZ

0

(ESP RS485 & ESP RS485Q), or LPZ

0

(ESP SL RS485) protect against flashover (typically the service entrance

location) through to LPZ 3. Available as standard ESP RS485 format, or

compact ESP RS485Q and Slim Line ESP SL RS485 versions for installations

where a high number of lines require protection.

Application

Connect in series with the signal line either near where it

enters or leaves the building or close to the equipment being

protected ensuring it is very close to the system’s earth star

point. Install protectors either within an existing cabinet/

cubicle or in a separate enclosure.

Replacement module for ESP SL RS485:

ESP SLRS485/M

Standard module replacement

ESP SLRS485/B

Base replacement

Combined Mounting/Earthing kits for ESP

RS485:

CME 4

For up to 4 x ESP RS485

CME 8

For up to 8 x ESP RS485

CME 16

For up to 16 x ESP RS485

CME 32

For up to 32 x ESP RS485

Full product range order codes can be found on pages 17/8-17/9

ESPRS485

ESPRS485

ESP RS485 installed in series

DIRTY

CLEAN

From line

To equipment

Earth

1

S

2

3

S

4

LightningBarrier

From line

LINE

CLEAN

Earth

To equipment

Furse

Wilford Road,

Nottingham,

NG21EB,UK

Clean

Line

Nominal voltage

Maxworking voltage,U

c

Current rating

In-line resistance

Max surge current

Let-through voltage,U

p

30V

36.7V

750mA

1.0

20kA

63V

ESP SL RS485 installed in series

rom line

To equipment

LINE

CLEAN

Earth

DIRTY

CLEAN

ESP RS485Q installed in series (in-line)

From line

To

equipment

Earth

Features & benefits

–– Very low let-through voltage (enhanced protection to

IEC/BS EN 62305) between all lines - Full Mode protection

–– Full Mode design capable of handling partial lightning

currents as well as allowing continual operation of

protected equipment

–– Repeated protection in lightning intense environments

–– 45 MHz bandwidth greatly exceeds 12 Mbps maximum

speeds

–– Low in-line resistance minimizes reductions in signal

strength

–– Suitable for earthed or isolated screen systems

–– Built-in DIN rail foot for simple mounting to top hat DIN rails

–– Convenient earthing through DIN foot and/or earth terminal

–– ESP RS485 can be flat mounted on base or side

–– ESP RS485 and ESP RS485Q have colour coded terminals

for quick and easy installation check

–– ESP SL RS485 has ultra slim 7 mm width ideal for compact

protection of large numbers of lines (e.g. process control

installations)

–– ESP SL RS485 includes two stage removable protection

module with simple quick release mechanism allowing

partial removal for easy line commissioning and

maintenance as well as full removal for protection

replacement

–– ESP SL RS485 includes optional LED status indication

–– Add L suffix to part number - i.e. ESP SL RS485L

Accessories