Table of Contents Table of Contents
Previous Page  240 / 336 Next Page
Information
Show Menu
Previous Page 240 / 336 Next Page
Page Background

12/14

Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

12

Data & signal protection

ESP SL X Series

Combined Category D, C, B tested protector (to BS EN 61643) suitable for

twisted pair signalling applications within hazardous environments

(ATEX/IECEx approved). Available for working voltages of up to 15 and 30

Volts. For use at boundaries up to LPZ

0

to protect against flashover through

to LPZ 3 to protect sensitive electronic equipment.

Features & benefits

–– Approved for use in hazardous environments for the

protection of Intrinsically Safe circuits (Classification: II 2(1)

G, Ex ia (ia Ga) IIC T4 Gb)

–– Very low let-through voltage (enhanced protection to

IEC/BS EN 62305) between all lines - Full Mode protection

–– Full Mode design capable of handling partial lightning

currents as well as allowing continual operation of

protected equipment

–– Repeated protection in lightning intense environments

–– Ultra slim 7 mm width ideal for compact protection of large

numbers of lines (e.g. process control installations)

–– Optional LED status indication versions available for low

current DC power applications

–– Negligible self-capacitance and self-inductance

offering minimal interference when protecting Intrinsically

Safe circuits

–– Very low (1 Ω) in-line resistance allows resistance critical

applications (e.g. alarm loops) to be protected

–– High (750 mA) maximum running current

–– High bandwidth enables higher frequency (high traffic or bit

rate) data communications

–– Screen terminal enables easy connection of cable screen

to earth

–– Suitable for earthed or isolated screen systems - add /I

suffix to part number for versions that require isolated screens

–– Built-in innovative DIN rail foot with locking feature for

simple positioning and clip-on mounting to top hat DIN rails

–– 4 mm

2

terminals allow for larger cross section wiring,

stranded wires terminated with ferrules or fitting two wires

into a single terminal

–– Approval references for ESP SL X Series: IECEx SIR

10.0030X, Sira 10ATEX2063X

Application

Use these protectors in hazardous environments where

installation space is at a premium and large numbers of lines

require protection (e.g. process control, 4-20 mA loops,

fire and gas detectors and shut-down systems). Suitable

for high speed digital communication equipment or systems

with long signal lines. See Furse Application Note AN013.

Installation

Connect in series with the data communication or signal

line either near where it enters or leaves the building or close

to the equipment being protected (e.g. within its control

panel). Either way, it must be very close to the system’s earth

star point. Install protectors either within an existing

cabinet/cubicle or in a separate enclosure.

NOTE:

Use the standard ESP SL ‘Slim Line’ Series for non-hazardous areas. The ESP SL Series is also available for protection of 3-wire, RS 485, RTD

& telecommunication applications (ESP SL/3W, ESP SL RS485, ESP SL RTD & ESP SL TN).

1

S

2

3

S

4

LightningBarrier

From line

LINE

CLEAN

Earth

To equipment

Furse

Wilford Road,

Nottingham,

NG2 1EB,UK

Clean

Line

Nominal voltage

Maxworking voltage,U

c

Current rating

In-line resistance

Max surge current

Let-through voltage,U

p

30V

36.7V

750mA

1.0

20kA

63V

From line

To equipment

LINE

CLEAN

Earth

Accessories

Replacement modules:

ESP SL15X/M, ESP30X/M

Standard module replacement for 15 and

30 V protectors respectively

ESP SL15XL/M, ESP30XL/M

LED module replacement for 15 and 30 V

protectors respectively

ESP SLX/B

Base replacement (common for standard

and LED modules)

ESP SLX/I/B

Base replacement with isolated screen

from earth

Full product range order codes can be found on pages 17/8-17/9