Total Solution to Earthing & Lightning Protection |
9AKK106354A3360
12/11
12
ESP D/BX Series - Technical specification
ESP 06D/BX
ESP 15D/BX
ESP 30D/BX
ESP 50D/BX
ESP 110D/BX
ESP TN/BX
Electrical specification
ESP 06D/2BX
ESP 15D/2BX
ESP 30D/2BX
ESP 50D/2BX
ESP 110D/2BX
ESP TN/2BX
ABB order code
7TCA085400R0081 7TCA085400R0091 7TCA085400R0101 7TCA085400R0113 7TCA085400R0006 7TCA085400R0175
7TCA085400R0080 7TCA085400R0090 7TCA085400R0100 7TCA085400R0111 7TCA085460R0343 7TCA085400R0172
Nominal voltage
(1)
6 V
15 V
30 V
50 V
110 V
–
Maximum working voltage
U
c (RMS/DC)
(2)
5 V / 7.79 V
13 V / 19 V
26 V / 37.1 V
41 V / 58 V
93 V / 132 V
– / 296 V
Current rating (signal)
300 mA
In-line resistance (per line ±10%)
9.4 Ω
9.4 Ω
9.4 Ω
9.4 Ω
9.4 Ω
4.4 Ω
Bandwidth (-3 dB 50 Ω system)
800 kHz
2.5 MHz
4 MHz
6 MHz
9 MHz
20 MHz
ESP 06D/BX
ESP 15D/BX
ESP 30D/BX
ESP 50D/BX
ESP 110D/BX
ESP TN/BX
Transient specification
ESP 06D/2BX
ESP 15D/2BX
ESP 30D/2BX ESP 50D/2BX
ESP 110D/2BX
ESP TN/2BX
Let-through voltage (all conductors)
(3)
U
p
C2 test 4 kV 1.2/50 μs, 2 kA 8/20 μs to
BS EN/EN/IEC 61643-21
12.0 V
25.0 V
44.0 V
78.0 V
155 V
395 V
C1 test 1 kV, 1.2/50 μs, 0.5 kA 8/20 μs to
BS EN/EN/IEC 61643-21
11.5 V
24.5 V
43.5 V
76.0 V
150 V
390 V
B2 test 4 kV 10/700 μs to BS EN/EN/IEC 61643-21
10.0 V
23.0 V
42.5 V
73.0 V
145 V
298 V
5 kV, 10/700 μs
(4)
10.5 V
23.8 V
43.4 V
74.9 V
150 V
300 V
Maximum surge current
D1 test 10/350 μs to – Per signal wire
2.5 kA
BS EN/EN/IEC 61643-21: – Per pair
5 kA
8/20 μs to ITU-T K.45:2003, – Per signal wire
10 kA
IEEE C62.41.2:2002: – Per pair
20 kA
ESP 06D/BX
ESP 15D/BX
ESP 30D/BX
ESP 50D/BX
ESP 110D/BX
ESP TN/BX
Mechanical specification
ESP 06D/2BX
ESP 15D/2BX
ESP 30D/2BX
ESP 50D/2BX
ESP 110D/2BX
ESP TN/2BX
Temperature range
-40 to +80 °C
Connection type
Screw terminal - for IDC terminal use part number with /I - maximum torque 0.5 Nm
Conductor size (stranded)
1.5 mm
2
Earth connection
M6 stud - maximum torque 0.5 Nm
Cable glands
Accommodate 2.3-6.7 mm diameter cable (PG7)
Degree of protection (IEC 60529)
M6 stud
Case material
PVC
Weight: – Unit
0.3 kg
– Packaged (per 10)
0.35 kg
Dimensions
See diagram below
(1)
Nominal voltage (RMS/DC or AC peak) measured at < 10 μA
(ESP 15D/BX, ESP 15D/2BX, ESP 30D/BX, ESP 30D/2BX,
ESP 50D/BX, ESP 50D/2BX, ESP 110D/BX, ESP 110D/2BX)
and < 200 μA (ESP 06D/BX & ESP 06D/2BX)
(2)
Maximum working voltage (RMS/DC or AC peak) measured at
< 1 mA leakage (ESP 15D/BX, ESP 15D/2BX, ESP 30D/BX,
ESP 30D/2BX, ESP 50D/BX, ESP 50D/2BX, ESP 110D/BX,
ESP 110D/2BX), < 10 mA (ESP 06D/BX, ESP 06D/2BX) and
< 10 μA (ESP TN/BX, ESP TN/2BX)
(3)
The maximum transient voltage let-through of the protector
throughout the test (±10%), line to line & line to earth,
both polarities. Response time < 10 ns
(4)
Test to IEC 61000-4-5:2006, ITU-T (formerly CCITT) K.20,
K.21 and K.45,Telcordia GR-1089-CORE, Issue 2:2002,
ANSI TIA/EIA/IS-968-A:2002 (formerly FCC Part 68)
Depth:
56 mm
120 mm
25 mm
25 mm max.
80 mm
108 x 50 mm
M4 clearance
Data & signal protection
ESP D/BX Series