D-23

Additional information

Electrical characteristics

Compact NS630b to NS1600

Vertical mounting

Front or rear connection

Top or bottom incoming

Vertical busbars on the left or right

Linergy LGY busbars

DD383537.eps

Using the data below, it is possible to determine the permissible current for a

prefabricated connection between a vertical Compact NS630b/NS1600, fixed or

withdrawable, and Linergy LGY busbars depending on the ambient temperature

around the switchboard and the IP value.

Fixed

Prefabricated connection

Device and cat. no.

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NS630b 3P cat. no. 04485 630

630

630

630

630

630

630

630

630

630

630

bb

4P cat. no. 04486

NS800 3P cat. no. 04485 800

800

800

800

800

800

800

800

800

800

800

bb

4P cat. no. 04486

NS1000 3P cat. no. 04485 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

bb

4P cat. no. 04486

NS1250 3P cat. no. 04485 1250 1250 1250 1250 1250 1250 1250 1200 1250 1150 1200

bb

4P cat. no. 04486

NS1600 3P cat. no. 04487 1600 1550 1600 1500 1550 1450 1500 1400 1450 1350 1400

bb

4P cat. no. 04488

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Withdrawable

Prefabricated connection

Device and cat. no.

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NS630b 3P cat. no. 04477 630

630

630

630

630

630

630

630

630

630

630

bb

4P cat. no. 04478

NS800 3P cat. no. 04477 800

800

800

800

800

800

800

800

800

800

800

bb

4P cat. no. 04478

NS1000 3P cat. no. 04477 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

bb

4P cat. no. 04478

NS1250 3P cat. no. 04477 1250 1250 1250 1250 1250 1250 1250 1200 1250 1150 1200

bb

4P cat. no. 04478

NS1600 3P cat. no. 04491 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330

bb

4P cat. no. 04492

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Example:

For a fixed Compact NS1600, 4P, where the ambient temperature around

the switchboard is 35°C and the IP > 31:

the maximum permissible current for the prefabricated connection (04488) is 1450 A.

Designing connections between

a device and busbars

Prefabricated connections for

Compact NS630b to NS1600